FLUSH HORIZ. SIDEWALL SPRINKLERS, RES/QR-EC/EC

MODEL F993 AQUARIUS

®

, 5.6 K-FACTOR

GENERAL DESCRIPTION

The 5.6 K-Factor, Model F993 Aquar-
ius RES/QR-EC/EC Horizontal Side-
wall Sprinklers (Ref. Figure A) are
automatic sprinklers of the fusible sol-
der type. They are low profile, flush
mounting sprinklers which are in-
tended to be used in

wet pipe residential sprinkler sys-
tems for one- and two-family dwell-
ings and mobile homes per NFPA
13D,

wet pipe residential sprinkler sys-
tems for residential occupancies up
to four stories in height per NFPA
13R,

wet pipe sprinkler systems for the
residential portions of any occu-
pancy per NFPA 13,

light hazard, quick response — ex-
tended coverage (QR-EC) sprinkler
system applications per NFPA 13,
and

light hazard, extended coverage
(EC) sprinkler system applications
per NFPA 13.

Small and attractive, the F993 Sprin-
klers are installed with a Push-on Es-
cutcheon Plate and feature a smooth,
low profile, flush-style design with an
aesthetically pleasing appearance that
blends in with all types of surround-
ings. They are designed for installation
along a wall or lintel and just beneath
a smooth and level ceiling. Horizontal
sidewall sprinklers are generally used
in lieu of pendent or upright sprinklers
because of aesthetic, building con-
struction, or installation economy con-
siderations.

The 1/4 inch adjustment provided by
the Push-on Escutcheon Plate and the
additional 1/4 inch of adjustment that
can be obtained by use of the Exten-
sion reduces the accuracy to which the
sprinklers must be positioned. The 3
inch outside diameter of the Push-on
Plate also contributes to the ease of
installation by covering offset clear-
ance holes.

The F993 Sprinklers have been de-
signed to operate with a particular fus-
ible element temperature rating  and
heat sensitivity characteristic, as well
as to discharge water in a specific pat-
tern and quantity per square foot rela-
tionship. The combination of the per-
formance characteristics which are
associated with  the F993 Sprinklers
have been proven to help in the control
of residential type fires and, therefore,
to improve the chance for occupants to
escape or be evacuated.

FIGURE A

5.6 K-FACTOR MODEL F993 AQUARIUS (SIN G8993) RES/QR-EC/EC

HORIZONTAL SIDEWALL SPRINKLERS

NOTE:

The Fusible Element Assembly (consisting of Components 5 through 14)
falls out of he Body upon sprinkler operation.

Printed in U.S.A. 7-02

TD591

COMPONENTS:

1 - Dust Cap
2 - Arms
3 - Body
4 - Gasketed

Button-
Deflector

5 - Retaining

Ring

6 - Heat

Collectors

7 - Inner Loading

Plate

8 - Outer Loading

Plate

9 - Loading

Screw

10 - Solder Element
11 - Disc Spring
12 - Insulating

Washer

13 - Tamper

Resistant
Plug

14 - Spacer

PUSH-ON PLATE

WITH EXTENSION

PUSH-ON

PLATE

TYCO FIRE PRODUCTS

, 7071 S. 13th Street, Suite 103 Oak Creek, WI 53154 — www.gemsprinkler.com

Customer Service/Sales:

Tel: (800) 558-5236 / Fax: (800) 877-1295

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

S

P

RINKLERS

F

OR

REPLACEMENT

USE

O

NLY

IN

EXISTING

SPRINKLER

SYSTEMS

OBSOLETE

Summary of Contents for AQUARIUS F993

Page 1: ...e and the additional 1 4 inch of adjustment that can be obtained by use of the Exten sion reduces the accuracy to which the sprinklers must be positioned The 3 inch outside diameter of the Push on Pla...

Page 2: ...ontal Side wall Sprinklers are available in a 160 F 71 C temperature rating and they are rated for use at a maximum service pressure of 175 psi They are available with a chrome white or bright brass f...

Page 3: ...mum amount of water which must be discharged from an operat ing sprinkler the maximum area which can be covered by the spray from an oper ating sprinkler installation requirements necessary to the pro...

Page 4: ...be located above an elevation as shown in Figure E where they will not inter fere with the proper distribution of water by the sprinkler The F993 Sprinklers must NOT be lo cated a along wall overhang...

Page 5: ...inkler with the attached Protec tive Cap as shipped into the sprin kler fitting 4 Using the Model F873 Sprinkler Wrench shown in Figure G tighten the Sprinkler into the fitting The word TOP on the Def...

Page 6: ...e re placed The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards...

Page 7: ...stated under WARNINGS Alter the new construction and or the sprin kler system to suit the requirements of this document ORDERING PROCEDURE Orders for the Model F993 Aquarius RES QR EC EC Horizontal Si...