background image

Cap will prevent proper opera-

tion of the Sprinkler.

7. When using the Push-on Escutch-

eon Plate alone, align the two slots
on the inside edge of the Push-on
Escutcheon Plate with the Wrench
Lugs on the Sprinkler Body and then
push the Escutcheon Plate over the
Body of the Sprinkler until its outside
edge comes in  contact with  the
mounting surface.

When using the Push-on Plate with
Extension, first determine the dis-
tance from the wall mounting sur-
face to the outside of the Heat Col-
lector. If the dimension is 1-1/8
inches or less, discard the Extension
and proceed to install the Push-on
Plate as indicated above. If the di-
mension is greater than 1-1/8
inches, assemble the Extension to
the Push-on Plate and then proceed
to install the assembly as indicated
above.

NOTE

Do not attempt to make-up for

insufficient adjustment in an

Escutcheon Plate by under- or

over-tightening the Sprinkler.

Readjust the position of the

sprinkler fitting to suit.

CARE AND MAINTENANCE

The Model F993 Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:

NOTES

Absence of an Escutcheon Plate

may delay the time to sprinkler

operation in a fire situation.

Before closing a fire protection

system main control valve for

maintenance work on the fire pro-

tection system which it controls,

permission to shut down the af-

fected fire protection systems

must be obtained from the proper

authorities and all personnel who

may be affected by this action

must be notified.

Particular care to prevent over-

heating must be exercised when

storing sprinklers in cars, trucks,

trains, or other vehicles on warm,

bright sunny days.

Sprinklers which are found to be leak-
ing or exhibiting visible signs of cor-
rosoin must be replaced.

Automatic sprinklers  must  never  be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.

It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

The F993 Sprinklers must only be re-
placed with pendent sprinklers which
are listed for residential fire protection
service and which have the same
nominal K-factor, the same coverage
area, and the same or lower flow rat-
ings (as indicated under “Hydraulic
Design Criteria”).

All residential sprinklers installed
within a compartment (as defined by
the NFPA) must have the same heat
response thermal characteristic, and
their temperature ratings are to  be
within 10°F of each other.

NOTES

Wet pipe sprinkler systems must

be maintained at a minimum tem-

perature of 40F/4C. Exposure to

freezing temperatures can result

in bursting of the pipe and/or

sprinkler.

Do NOT enclose sprinklers within

drapes, curtains, or valances.

Do NOT hang anything from the

sprinklers.

Automatic sprinklers are NOT to

be tested with a heat source. Op-

eration of the heat responsive

element (Bulb) can result.

Do NOT cleanse the sprinklers

with soap and water, detergents,

ammonia, cleaning fluids, or

other chemicals. Remove dust,

lint, cobwebs, cocoons, insects,

and larvae by gently brushing

with a feather duster or gently

vacuuming with a soft bristle (i.e.,

dusting) brush attachment.

The minimum vertical clearance

between the tops of free standing

partitions, room dividers, cab-

inets, storage racks, stock piles,

etc., and the sprinkler deflector is

NOT to be less than the clearance

given below.

Horizontal Distance Vertical

from Sprinkler

Clearance

to Item, ft.

In.

More than 9 . . . . . . . 40

From 6 to 9 . . . . . . . . 32

Between 3 and 6 . . . . . 26

3 or Less . . . . . . . . . 18

Exercise suitable safety precau-

tions in the use and storage of

highly flammable and potentially

explosive materials. The rapid

rate of fire development and

spread which can be caused by

such materials can reduce the

ability of the sprinkler system to

aid in the control of a fire in

which they are involved.

—6—

OBSOLETE

Summary of Contents for AQUARIUS F993

Page 1: ...e and the additional 1 4 inch of adjustment that can be obtained by use of the Exten sion reduces the accuracy to which the sprinklers must be positioned The 3 inch outside diameter of the Push on Pla...

Page 2: ...ontal Side wall Sprinklers are available in a 160 F 71 C temperature rating and they are rated for use at a maximum service pressure of 175 psi They are available with a chrome white or bright brass f...

Page 3: ...mum amount of water which must be discharged from an operat ing sprinkler the maximum area which can be covered by the spray from an oper ating sprinkler installation requirements necessary to the pro...

Page 4: ...be located above an elevation as shown in Figure E where they will not inter fere with the proper distribution of water by the sprinkler The F993 Sprinklers must NOT be lo cated a along wall overhang...

Page 5: ...inkler with the attached Protec tive Cap as shipped into the sprin kler fitting 4 Using the Model F873 Sprinkler Wrench shown in Figure G tighten the Sprinkler into the fitting The word TOP on the Def...

Page 6: ...e re placed The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards...

Page 7: ...stated under WARNINGS Alter the new construction and or the sprin kler system to suit the requirements of this document ORDERING PROCEDURE Orders for the Model F993 Aquarius RES QR EC EC Horizontal Si...

Page 8: ...O B S O L E T E...

Reviews: