side of the Heat Collector. The Exten-
sion is used when this distance (Ref.
“D” in Figure D) is greater than 1-1/8
inches and, the Extension is discarded
for distances of 1-1/8 inches or less.

The Push-on Escutcheon Plate and
Extension are formed from low carbon
sheet steel and they are available with
a chrome or white finish. Also, a color
finish other than white can  be pro-
vided.

NOTE

The Push-on Escutcheon Plates

shown in Figures C and D can

NOT be used to hold the F993 in

position. The F993 must be se-

cured in position by firmly fasten-

ing the sprinkler system piping to

the dwelling structure. If the F993

is not properly secured in posi-

tion, reaction forces resulting

from sprinkler operation could

alter its orientation and water

distribution pattern.

QR-EC & EC

INSTALLATION/USAGE CRITERIA

When used in QR-EC (quick response
— extended coverage) or EC (ex-
tended coverage) applications, Model
F993 Aquarius RES/QR-EC/EC Hori-
zontal Sidewall Sprinklers must only
be installed and utilized in Light Haz-
ard Occupancies, under smooth and
level ceilings and in accordance with
the criteria given in Table A.

NOTES

For coverage area dimensions

less than those indicated in Table

A, it is necessary to use the mini-

mum required flow for the highest

width (W) and length (L) for

which installation criteria are

stated.

The F993 Sprinklers must NOT be

used with beams, joists, or ducts

located within the sprinkler cov-

erage area. They may be located

along the boundaries separating

adjacent sprinkler coverage ar-

eas.

RESIDENTIAL

INSTALLATION/USAGE CRITERIA

When used in residential applications,
the Model F993 Aquarius RES/QR-
EC/EC Horizontal Sidewall Sprinklers
must only be installed and utilized in
accordance with the following de-
scribed criteria which are provided by
the manufacturer.

These restrictions relate to

the general service conditions nec-

essary to sprinkler performance and
integrity,

the minimum amount of water which
must be discharged from an operat-
ing sprinkler,

the maximum area which can  be
covered by the spray from an oper-
ating sprinkler,

installation requirements necessary
to the proper operational sensitivity
of the sprinklers,

preventing the wetting (i.e., cold sol-
dering) of the Fusible Element As-
sembly of a non-operated sprinkler,
which is adjacent to one which has
operated, and

preventing the weakening followed
by the possible release of a sprin-
kler’s Fusible Element Assembly,
due to exposure to heat sources
other than abnormal fire.

NOTES

1. Residential Fire Sprinkler Sys-

tems should only be designed

and installed by those compe-

tent and completely familiar

with automatic sprinkler sys-

tem design, installation proce-

dures, and techniques.

2. Several criteria may apply to

the installation and usage of

each sprinkler. Consequently,

it is recommended that the

NFPA 13D/13R

NFPA 13D/13R

NFPA 13

MINIMUM

MINIMUM

EC

SINGLE HEAD

(e)

MULTIPLE HEAD

(e)

MINIMUM

W x L

FLOW

FLOW

FLOW

A

B

FT x FT

GPM (psi)

(d)

GPM (psi)

(d)

GPM (psi)

(d)

INCHES FEET

RES

(a)

12 x 12

22 (15.4)(e)

15.5 (7.7)

4 to 6

(f)

6

RES

(a)

14 x 14

30 (28.7)(e)

21(14.1)

4 to 6

(f)

7

QR-EC

(b)

14 x 16

26 (21.6)

4 to 6

(f)

7

EC

(c)

14 x 18

36 (41.3)

4 to 6

(f)

7

NOTES:

(a) Wet pipe fire sprinkler systems in the residential portions of any occupancy per NFPA

13, in one- and two- family dwellings and mobile homes per NFPA 13D, or residential
occupancies per NFPA 13R.

(b) For use in QR-EC and EC Light Hazard Occupancy automatic sprinkler system applica-

tions per NFPA 13.

(c) For use in EC Light Hazard Occupancy automatic sprinkler system applications per NFPA

13.

(d) Requirement is based on minimum flow in GPM from each sprinkler. The indicated

residual pressures are based on the nominal K-factor.

(e) Refer to Hydraulic Design Criteria under Residential Installation/Usage Criteria Section

for details.

(f) To meet this requirement, the centerline of the waterway (Ref. Fig. A) must be installed

between 4-5/8 and 6-5/8 inches below the ceiling.

TABLE A

HYDRAULIC DESIGN CRITERIA FOR

MODEL F993 AQUARIUS RES/QR-EC/EC

HORIZONTAL SIDEWALL SPRINKLERS

—3—

OBSOLETE

Summary of Contents for AQUARIUS F993

Page 1: ...e and the additional 1 4 inch of adjustment that can be obtained by use of the Exten sion reduces the accuracy to which the sprinklers must be positioned The 3 inch outside diameter of the Push on Pla...

Page 2: ...ontal Side wall Sprinklers are available in a 160 F 71 C temperature rating and they are rated for use at a maximum service pressure of 175 psi They are available with a chrome white or bright brass f...

Page 3: ...mum amount of water which must be discharged from an operat ing sprinkler the maximum area which can be covered by the spray from an oper ating sprinkler installation requirements necessary to the pro...

Page 4: ...be located above an elevation as shown in Figure E where they will not inter fere with the proper distribution of water by the sprinkler The F993 Sprinklers must NOT be lo cated a along wall overhang...

Page 5: ...inkler with the attached Protec tive Cap as shipped into the sprin kler fitting 4 Using the Model F873 Sprinkler Wrench shown in Figure G tighten the Sprinkler into the fitting The word TOP on the Def...

Page 6: ...e re placed The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards...

Page 7: ...stated under WARNINGS Alter the new construction and or the sprin kler system to suit the requirements of this document ORDERING PROCEDURE Orders for the Model F993 Aquarius RES QR EC EC Horizontal Si...