Fire sprinkler systems are not a substi-
tute for intelligent fire safety aware-
ness or construction materials and
practices required by building codes.

APPROVALS AND STANDARDS

The 5.6 K-Factor, Model F993 Aquar-
ius RES/QR-EC/EC Horizontal Side-
wall Sprinklers are listed by Underwrit-
ers

Laboratories

Inc.

and

Underwriters’ Laboratories of Canada.
The listings only apply to the service
conditions indicated in the General
Technical Data and Installation/Usage
sections.

The Model F993 Aquarius RES/QR-
EC/EC Horizontal Sidewall Sprinklers
are approved by the Scientific Serv-
ices Laboratory (Australia).

The Model F993 Aquarius RES/QR-
EC/EC Horizontal Sidewall Sprinklers
are approved by the New York City
Board of Standards and Appeals un-
der Calendar Number 334-79-SA.

Any questions concerning an interpre-
tation of NFPA 13, 13D, or 13R sprin-
kler system design/installation stand-
ards, as well as requests for system
design/installation standards not pres-
ently covered by NFPA 13, 13D, or
13R, should be addressed to the:

Secretary, Standards Council
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269

WARNINGS

The

Model

F993

Aquarius

RES/QR-EC/EC Horizontal Side-

wall Sprinklers described herein

must be installed and maintained

in compliance with this docu-

ment, as well as with the applica-

ble standards of the National Fire

Protection Association, in addi-

tion to the standards of any other

authorities having jurisdiction.

Failure to do so may impair the

integrity of these devices.

Because of the above cited stipu-

lations and the varied nature of

residential type architecture,

there will be some compartment

designs which cannot be fully

sprinklered in accordance with

the recommendations of NFPA 13,

13D, or 13R. In the event of this

condition, consult the authorities

having jurisdiction for guidance.

It is the responsibility of an in-

stalling contractor to provide a

copy of this document to the

owner or his representative and,

in turn, it is the obligation of the

owner to provide a copy of this

document to a succeeding owner.

The owner is responsible for

maintaining their fire protection

system and devices in proper op-

erating condition. The installing

contractor or sprinkler manufac-

turer should be contacted relative

to any questions.

GENERAL TECHNICAL DATA

Sprinkler Assemblies:

The 5.6 K-Factor, Model F993 Aquar-
ius RES/QR-EC/EC Horizontal Side-
wall Sprinklers are available in a
160°F/71°C temperature rating and
they are rated for use at a maximum
service pressure of 175 psi. They are
available with a chrome, white, or
bright brass finish. Escutcheon Plates
are available with various finishes and
are ordered separately, as indicated in
the following sub-section.

The F993 is shipped with a plastic Pro-
tective Cap covering the outside of the
Fusible Element and the outer portion
of the Body. The Protective Cap can
be left in position while the Sprinkler is
being installed and then it is slid off
once the wall installation is complete
and the sprinkler system is ready to be
put into service.

The nominal flow “Q” in GPM (LPM) is
determined by the following formula:

Q = K (p

1/2

)

where the nominal sprinkler discharge
coefficient “K” equals 5.6 (80,6); and
“p” equals the residual pressure in psi
(bar).

The Body is bronze per ASTM B584
(C83600 or C84400) and the Dust Cap
is polyolefin. The Heat Collectors are
copper per ASTM B152 (C11000) and
the Inner & Outer Loading Plates and
Spacer are brass per ASTM B16
(C36000) or ASTM B140 (C31400 or
C31600). The Loading Screw and two
Arms are Type 302 stainless steel per
ASTM A276 or Type 303 per ASTM
A582. The Disc Spring is a chrome
plated high strength carbon steel and
the Retaining Ring is titanium per
ASTM B348 (Grade 5). The Gasketed
Button-Deflector consists of brass but-
ton per ASTM B16 (C36000), brass
deflector per ASTM B36 (C22000),
and a Teflon

†

gasket.

Escutcheon Plates:

The following are the two types of es-
cutcheon plates that may be used with
the F993 Aquarius Sprinkler:

Push-on Escutcheon Plate

Push-on Escutcheon Plate with Ex-
tension

Figures C and D illustrate typical in-
stallations of an F993 using a Push-on
Escutcheon Plate and using a Push-on
Plate with Extension. The Push-on Es-
cutcheon Plate provides a total of 1/4
inch of horizontal adjustment and it is
installed by simply slipping it over the
F993 Body; however, when it is used
in conjunction with the Extension, an
additional 1/4 inch of adjustment can
be obtained for a total of 1/2 inch of
horizontal adjustment.

When using the Push-on Plate  with
Extension, the installer simply deter-
mines the approximate distance from
the wall mounting surface to the out-

Dim.

Inches

MM

A - Nom.

1-1/16

27.0

B -

2-1/4

57.2

C -

3

76.2

D - Min.

7/8

22.2

D - Nom.

1

25.4

D - Max.

1-1/8

28.6

FIGURE C

PUSH-ON ESCUTCHEON

PLATE

Dim.

Inches

MM

A - Nom.

15/16

23.8

B -

2-1/4

57.2

C -

3-1/8

79.4

D - Min.

7/8

22.2

D - Nom.

1-1/8

28.6

D - Max.

1-3/8

34.9

FIGURE D

PUSH-ON ESCUTCHEON

PLATE WITH EXTENSION

†

DuPont Registered Trademark

—2—

OBSOLETE

Summary of Contents for AQUARIUS F993

Page 1: ...e and the additional 1 4 inch of adjustment that can be obtained by use of the Exten sion reduces the accuracy to which the sprinklers must be positioned The 3 inch outside diameter of the Push on Pla...

Page 2: ...ontal Side wall Sprinklers are available in a 160 F 71 C temperature rating and they are rated for use at a maximum service pressure of 175 psi They are available with a chrome white or bright brass f...

Page 3: ...mum amount of water which must be discharged from an operat ing sprinkler the maximum area which can be covered by the spray from an oper ating sprinkler installation requirements necessary to the pro...

Page 4: ...be located above an elevation as shown in Figure E where they will not inter fere with the proper distribution of water by the sprinkler The F993 Sprinklers must NOT be lo cated a along wall overhang...

Page 5: ...inkler with the attached Protec tive Cap as shipped into the sprin kler fitting 4 Using the Model F873 Sprinkler Wrench shown in Figure G tighten the Sprinkler into the fitting The word TOP on the Def...

Page 6: ...e re placed The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards...

Page 7: ...stated under WARNINGS Alter the new construction and or the sprin kler system to suit the requirements of this document ORDERING PROCEDURE Orders for the Model F993 Aquarius RES QR EC EC Horizontal Si...