Input voltage:
24 V DC
Logic level "1":
> 15.3 V DC
Logic level "0":
< 5.8 V DC
Input current:
typically < 0.5 mA
7.7.3 Analogue output signals – Control module Positioner (code S0)
7.7.3.1 Actual value
Output signal:
0/4 - 20 mA; 0 - 10 V (function selectable via IO-Link)
Output type:
active
Accuracy:
≤ ±1% of full flow
Temperature drift:
≤ ±0.1% / 10°K
Load resistor:
≤ 750 kΩ
Resolution:
12 bit
Short-circuit proof:
Yes
7.7.4 Digital output signals
Outputs:
Function selectable via IO-Link (see table Overview of available functions – Input and output sig-
nals)
Type of contact:
Push-Pull
Switching voltage:
Power supply Uv
Switching current:
≤ 140 mA
Short-circuit proof:
Yes
7.7.5 Communication
Interface:
IO-Link
Function:
Parameterization/process data
Transmission rate:
38.4 kBaud
GEMÜ 543
Positioner (Code S0)
www.gemu-group.com
13 / 64
7 Technical data