Index
Sub-
Index
Access
rights
Parameter
Function
Factory
settings
Setting options
0x62
1
RO
Operating Time Open
Current operating time
OPEN
0
0 to 255
(0 to 25.5s)
2
RO
Operating Time Close
Current operating time
CLOSE
0
0 to 255
(0 to 25.5s)
0x90
2
R/W
Force
Force of average tra-
versing range and
sealing
6
1 to 6
3
R/W
Init Force
Force of initialization
3
1 to 6
0xB0
1
R/W
Reinforcement P kp
P component – posi-
tioner
200
1 to 200
(0.1 to 20.0)
2
R/W
Reinforcement D kD
D component – posi-
tioner
10
1 to 200
(0.1 to 20.0)
3
R/W
Derivative action time
Delay constant
0
0 to 100
(0 to 100 s)
4
R/W
Dead zone
Hysteresis
10
1 to 250
(0.1 to 25.0%)
0xB2
1
R/W
Open Tight
Sealing function valve
position OPEN
995
800 to 1000
(80.0 to 100.0%)
2
R/W
Close Tight
Sealing function valve
position CLOSED
5
0 to 200
(0 to 20.0%)
0xB4
1
R/W
Split Start
Set set value start
0
0 to Split End – 100
(0.0 to Split End –
10.0%)
2
R/W
Split End
Set set value end
1000
Split Start + 100 to
1000
(Split Start + 10.0% to
100.0%)
0xB6
1
R/W
Max Pos
Stroke limiter valve
position OPEN
1000
Min Pos to 1000
(Min Pos to 100.0%)
2
R/W
Min Pos
Stroke limiter valve
position CLOSED
0
0 to Max Pos
(0.0% to Max Pos)
0xB8
1
R/W
Set Value Direction
Set value direction set
value input
0
0 → Rise (rising)
1 → Fall (falling)
2
R/W
Set Value Type
Determine signal input
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
3
R/W
I Min W
Determine minimum
current input
35
0 to 40
(0 to 4.0 mA)
4
R/W
I Max W
Determine maximum
current input
205
200 to 220
(20.0 to 22.0 mA)
5
R/W
U Max W
Determine maximum
current input
103
100 to 110
(10.0 to 11.0 V)
0xBA
1
R/W
Analog Output Dir
Set value direction set
value output
0
0 → Rise (rising)
1 → Fall (falling)
2
R/W
Analog Output Type
Determine signal out-
put
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
3
R/W
Analog Out Min
Determine minimum
signal output
0
0 to Max
(0.0% to Max)
4
R/W
Analog Out Max
Determine maximum
signal output
1000
Min to 1000
(Min to 100%)
0xBC
0
R/W
Init Time
Set debounce time for
initialization start
150
50 to 5000
(50 to 5000 ms)
www.gemu-group.com
38 / 64
GEMÜ 543
Positioner (Code S0)
12 Specific data IO-Link (pin 6)