S.241 Acceleration 2
(linked to F.203)
0.60
0.01
5.00
Linear acceleration (m/s
2
) with ramp set 2.
S.242 Jerk acc end 2
(linked to F.256)
1.40
0.01 10.00
Jerk (m/s
3
) applied at the beginning of a deceleration with ramp set 2.
S.243 Jerk dec ini 2
(linked to F.257)
1.40
0.01 10.00
Jerk (m/s
3
) applied at the beginning of a deceleration with ramp set 2.
S.244 Deceleration 2
(linked to F.204)
0.60
0.01
5.00
Linear deceleration (m/s
2
) with ramp set 2.
S.245 Jerk dec end 2
(linked to F.258)
1.00
0.01 10.00
Jerk (m/s
3
) applied at the beginning of a deceleration with ramp set 2.
S.250 Cont close delay
(linked to A.080)
0.20
0.00 10.00
Delay time (s) for safe closing or the run contactor.
S.251 Magnet time
(linked to A.081)
1.00
0.00 10.00
Duration (s) of the initial magnetization of the motor with DC injection.
S.252 Brake open delay
(linked to A.082)
0.20
0.00 10.00
Delay time (s) between the open command and effective opening of the mechanical brake.
S.253 Smooth start dly
(linked to A.083)
0.00
0.00 10.00
Duration (s) of the smooth start phase.
S.254 DCBrake stp time
(linked to A.084)
1.00
0.00 10.00
Duration (s) of the stopping phase, after the speed has fallen below the zero threshold (defined by parameter P.440). During
this phase, the inverter can either output a DC current, or maintain a low frequency, in order to compensate for the slip
(default), as programmed by S.260.
S.255 Brake close dly
(linked to A.085)
0.20
0.00 10.00
Delay time (s) between the close command and the effective engagement of the mechanical brake.
S.256 Cont open delay
(linked to A.086)
0.20
0.00 10.00
Delay time (s) between the open command and the affective opening of the run contactor.
S.260 Lift stop mode
(linked to A.220)
[1] Normal stop
After the car speed falls below the zero threshold (defined by P.440), the inverter can be programmed to brake with DC
injection (S.260 = 0), or to maintain a low frequency output in order to compensate for the estimated slip (S.260 = 1). The
latter is set by default.
Possible selections:
[0] DC brake at stop
[1] Normal stop
S.300 Manual boost [%]
(linked to P.120)
3.0
0.0
25.0
Voltage boost (% of motor rated voltage) applied at low frequency in order to maintain the machine flux.
S.301 Auto boost en
(linked to P.122)
[0] Disable
The automatic boost allows for precise compensation of the resistive voltage drop due to the winding resistance, keeping the
flux at its rated value regardless of the load level and output frequency. For correct operation of this function, a precise value
of the equivalent stator resistance is needed.
Possible selections:
[0] Disable
[1] Enable
S.310 Slip compensat
(linked to P.100)
50
0
250
Amount of slip compensation (% of rated slip, calculated from nameplates) during motoring (power flows from motor to load).
S.311 Slip comp regen
(linked to P.102)
50
0
250
Code Display
(Description)
Def.
Min.
Max
Summary of Contents for SIEIDrive LIFT AGy -L
Page 1: ... Instruction manual SIEIDrive LIFT Lift vector AC Drives AGy L ...
Page 46: ...Italiano 46 AGy L ...
Page 90: ...English 90 AGy L ...
Page 134: ...Français 134 AGy L ...
Page 178: ...Deutsch 178 AGy L ...
Page 222: ...Español 222 AGy L ...
Page 240: ...NOTE ...
Page 241: ......