81906_MAN_GRP-H_02-2022_ENG_pag. 59
•
Parametri del dispositivo - Indici primari
Index
Sub-index
Name of the
object
Access
Length
Data
type
Value (exam-
ple)
Range of
values
Scale
factor Offset
Unit
Description
U
M
S
0x0040
0x00
Hb.E
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Enabling HB alarm
0x0041
0x00
Hb.m
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Enable memory for
HB alarm
0x0042
0x00
Hb.F
RO R/W R/W
2
UInt16
0 (default)
0, 1, 2
1
0
-
HB alarm function
0x0043
0x00
A.Hb
RO R/W R/W
2
UInt16
0 (default)
L.tA…H.tA
0.1
0
A
HB alarm threshold
0x0044
0x00
Hb.t
RO R/W R/W
2
UInt16
10 (default)
0…999
1
0
s
Delay time for HB
alarm activation
0x0045
0x00
Hb.P
RO R/W R/W
2
UInt16 90.0 (default)
0.0…100.0
1
0
%
HB alarm threshold
percentage
0x0046
0x00
Hb.tA
RO R/W R/W
2
UInt16
0 (default)
L.tA…H.tA
0.1
0
A
Current reading in HB
calibration
0x0047
0x00
Hb.tV
RO R/W R/W
2
UInt16
0 (default)
L.tV…H.tV
0.1
0
V
Voltage reading in HB
calibration
0x0048
0x00
Hb.Pw
RO R/W R/W
2
UInt16
0 (default)
0.0…100.0
1
0
%
Power read in HB
calibration
0x0049
0x00
hd.5
RO R/W R/W
2
UInt16
0 (default)
0, 1, 2, 3
1
0
-
Trigger modes
0x004A
0x00
bF.Cy
RO R/W R/W
2
UInt16
1 (default)
1…10
1
0
-
Minimum number of
Burst Firing cycles
0x004B
0x00
PS.E
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Soft start enabling
0x004C
0x00
PS.tm
RO R/W R/W
2
UInt16 10.0 (default)
0.1…60.0
0.1
0
s
Soft start ramp du-
ration
0x004D
0x00
PS.oF
RO R/W R/W
2
UInt16
2 (default)
0…999
1
0
s
Soft start ramp reacti-
vation time
0x004E
0x00
FA.P
RO R/W R/W
2
UInt16
0 (default)
0.0…100.0
1
0
%
Fault Action Power
0x004F
0x00
tyP
RO R/W R/W
2
UInt16
1 (default)
0, 1, 2, 3, 4,
5, 6
1
0
-
Analogue input type
0x0050
0x00
Lo.S
RO R/W R/W
2
Int16
0 (default)
-100.0…
200.0
0.1
0
-
Analogue input scale
minimum limit
0x0051
0x00
HI.S
RO R/W R/W
2
Int16
1000
(default)
Lo.S…200.0
1
0
-
Analogue input scale
maximum limit
0x0052
0x00
FLt
RO R/W R/W
2
UInt16
0.1 (default)
0.0…20.0
0.1
0
s
Analog input signal
digital low-pass filter
0x0053
0x00
F.tA
RO R/W R/W
2
UInt16
0.1 (default)
0.0…20.0
0.1
0
s
Current reading low
pass digital filter
0x0054
0x00
F.tV
RO R/W R/W
2
UInt16
2.0 (default)
0.0…20.0
0.1
0
s
Voltage reading low
pass digital filter
0x0055
0x00
oFS
RO R/W R/W
2
UInt16
0 (default)
0.0…99.9
0.1
0
-
Analogue input cor-
rection offset
0x0056
0x00
o.tA
RO R/W R/W
2
UInt16
0 (default)
0.0…99.9
0.1
0
A
Current reading cor-
rection offset
0x0057
0x00
o.tV
RO R/W R/W
2
UInt16
0 (default)
0.0…99.9
0.1
0
V
Voltage reading cor-
rection offset
0x0058
0x00
U.tV
RO R/W R/W
2
UInt16
10 (default)
0…999
1
0
s
Voltage reading upda-
te time
0x0059
0x00
out.1
RO R/W R/W
2
UInt16
5 (default)
0, 1, 2, 3, 4,
5, 6, 7
1
0
-
Reference for output 1
0x005A
0x00
out.1.t
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Output type 1
0x005B
0x00
out.2
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Reference for output
2 (*)
0x005C
0x00
Ct
RO R/W R/W
2
UInt16
2.0 (default)
0.1…30.0
0.1
0
s
SSR output cycle time
0x005D
0x00
hd.2
RO R/W R/W
2
UInt16
7 (default)
0, 1, 2, 3, 4,
5, 6, 7
1
0
-
Enabling Power Fault
alarms
0x005E
0x00
PF.m
RO R/W R/W
2
UInt16
0 (default)
0, 1
1
0
-
Enable memory for
Power Fault alarms
0x005F
0x00
dG.t
RO R/W R/W
2
UInt16
10 (default)
1…999
1
0
s
SSR_SHORT update
time
0x0060
0x00
dG.F
RO R/W R/W
2
UInt16
10 (default)
0…99
1
0
s
NO_VOLTAGE and
NO_CURRENT alarm
filter
0x0061
0x00
but
RO R/W R/W
2
UInt16
1 (default)
0, 1
1
0
-
Front key enabling