81906_MAN_GRP-H_02-2022_ENG_pag. 57
•
Default parameters - Identification
Index
Sub-index
Name of the
object
Access
Length
Data
type
Value (example)
Description
U
M
S
0x0010
0x00
VendorName
RO
RO
RO
10
String
GEFRAN spa
0x0011
0x00
VendorText
RO
RO
RO
14
String
0x0012
0x00
ProductName
RO
RO
RO
Max64
String
GRP-120-48-I-1-x-
x-x-x-x
Full product description
0x0013
0x00
ProductID
RO
RO
RO
12
String
GRP-xxxxxxxxx
Model type
0x0014
0x00
ProductText
RO
RO
RO
Max30
String
Single-phase Solid
State Relay
Functional description of
the product
0x0015
0x00
SerialNumber
RO
RO
RO
8
String
20400102
Product serial number
0x0016
0x00
HardwareRevision
RO
RO
RO
3
String
1.0
0x0017
0x00
FirmwareRevision
RO
RO
RO
3
String
1.1
Software version
0x0018
0x00
ApplicationSpeci-
ficTag
RO RW RW
Max32
String
*** (Default)
The user can specify the function
and location of the device in the
system in the tag
0x0019
0x00
FunctionTag
RO RW RW
Max32
String
Vuoto (Default)
The user can specify the function
and location of the device in the
system in the tag
0x001A
0x00
LocationTag
RO RW RW
Max32
String
Vuoto (Default)
The user can specify the function
and location of the device in the
system in the tag
U = User, M = Maintenance technician, S = Specialist
•
Default parameters - Diagnosis
Index
Sub-index
Name of the
object
Access
Length
Data type
Value (example)
Description
U
M
S
0x0020
0x00
ErrorCount
RO
RO
RO
2
UInt16
0
Incremental counter of
errors from power-on
0x0024
0x00
DeviceStatus
RO
RO
RO
1
UInt8
See the following
table (Device Status
Values)
Defines the status of the
device
0x0025
0x01
0x02
0x03
0x04
DetailedDevice-
Status
RO
RO
RO
Variable
(Array di 4 ele-
menti, 3 bytes
per elemento)
See the following
Tables (Errors and
warnings in the De-
tailed Device Status
and Error Code)
Specifies the detailed sta-
tus of the Device:
Octet 1 = EventQualifier
(see IO-Link standard)
Octet 2, 3 = EventCode
See tables below
0x0028
0x00
ProcessDataInput
RO
RO
RO
PD length
PD
0
Read the last valid Pro-
cess Data from the PDin
channel
•
Values of the Device Status
Value
Description
0x00
The device works correctly (no error / warning)
0x01
Maintenance required
0x02
Out of specification
0x03
Functional check
0x04
Failure