81906_MAN_GRP-H_02-2022_ENG_pag. 36
4.2.2.2. Enable memory for Power Fault alarms
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
PF.m
Alarms
PF alarms
R/W
■
-
0
Enable memory for Power Fault alarm: after the causes that triggered the PF alarms have
disappeared, the alarms remain on until reset by key, serial line or IO-Link.
Options:
0 Disabled
1 Enabled
4.2.2.3. SSR_SHORT update time
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
dG.t
Alarms
PF Alarms
R/W
■
s
10
SSR_SHORT alarm update or wait (in seconds) for alarm activation.
min...max
: 1 ...999 s
4.2.2.4. NO_VOLTAGE and NO_CURRENT alarm filter
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
dG.F
Alarms
PF Alarms
R/W
■
s
10
Time filter for NO_VOLTAGE and NO_CURRENT alarms
Note: it is recommended to set a value not lower than the cycle time.
min...max
: 0 ...99 s