81906_MAN_GRP-H_02-2022_ENG_pag. 34
4.2.1.13.
HB alarm threshold percentage
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Hb.P
Alarms
HB Alarm
R/W
■
%
90.0
HB alarm threshold percentage of the current read in HB calibration.
Recommended values for the number of equal parallel loads controlled by a single SSR:
no. loads
Recommended percentage Hb.P
1 load
50.0%
2 loads
75.0%
3 loads
83.0%
4 loads
87.0%
5 loads
90.0%
6 loads
92.0%
7 loads
93.0%
8 loads
94.0%
min...max
: 0.0 ...100.0%
4.2.1.14.
Current reading in HB calibration
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Hb.tA
Alarms
HB Alarm
R/W
■
A
0.0
Current value read during the HB calibration procedure.
4.2.1.15.
Voltage reading in HB calibration
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Hb.tV
Alarms
HB Alarm
R/W
■
A
0.0
Voltage value read during the HB calibration procedure.
4.2.1.16.
Power read in HB calibration
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Hb.Pw
Alarms
HB Alarm
R/W
■
A
0.0
Power value read during the HB calibration procedure.