81906_MAN_GRP-H_02-2022_ENG_pag. 49
4.7.3.6. SSR output cycle time
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Ct
Power Control
R/W
■
s
2.0
SSR output cycle time in fixed cycle time (FCT) mode.
Example: if set to 10.0 if the requested power to be supplied is 75.0%, the On phase (SSR operating)
will last 7.5 s, the Off phases (SSR not operating) will last 2.5 s.
min...max
: 0.1 ... 30.0 s
4.7.1.
Soft start ramp settings
For GRP-H-x-x-x-1-x-x-2-x-x and GRP-H-x-x-x-1-x-x-
3-x-x models only
It can be enabled in either phase control or pulse train
mode and controls the conduction angle.
It is enabled through the PS.E. parameter
The soft start ramp, always in Phase Angle, starts
from a conduction angle and reaches 100.0% in a
time set in the PS.tm parameter from 0.1 to 60.0 s.
Soft start ends before the defined time if the power
reaches the corresponding required value set in
manual control or calculated by the analogue input.
The soft start ramp triggers at first start up after
power-on. It can be reactivated automatically if the
OFF condition occurs for a time longer than that
which can be set in PS.oF (if = 0 the function is as if it
were disabled).
.
4.7.1.1. Soft start enabling
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
PS.E
Power Control
R/W
■
-
0
Soft start ramp enabling.
Options:
0
Disabled
1
Enabled
4.7.1.2. Soft start ramp duration
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
PS.tm
Power Control
R/W
■
s
10.0
Phase soft start ramp duration.
min...max: 0.1 ... 60.0