81906_MAN_GRP-H_02-2022_ENG_pag. 54
5.3. CONTROL MODE
5.3.1.
IO-Link information
Port class
A
Baud rate
COM2 (38.4 kbit/s)
IO-Link version (1)
1.1
Profile
Common profile
Process data input length
% power supplied: 2 bytes
Ld.A (load current): 2 bytes
Ld.V (load voltage): 2 bytes
Ld.P (load power): 2 bytes
Ld.I (load impedence): 2 bytes
STATUS2: 2 bytes
for diagnostics:
STATUS2_NO_CURRENT: 1 bit
STATUS2_NO_VOLTAGE: 1 bit
STATUS2_SSR_SHORT: 1 bit
STATUS2_HB: 1 bit
STATUS2: 2 bytes
for diagnostics:
STATUS3_CURRENT_SENSOR_BROKEN: 1 bit
STATUS3_FREQUENCY_WARNING: 1 bit
STATUS3_SCR_OVER_HEAT: 1 bit
STATUS3_SCR_TEMP_SENSOR_BROKEN: 1 bit
Process data output length
% Power to be supplied: 2 bytes
Min cycle time
20ms
SIO mode
Supported
ISDU
Supported
Database
Supported
(1)
Compliant with IO-Link Interface Specification v.1.1.2 (July 2013)
5.3.2.
SIO mode and IO-Link mode
The static group supports both SIO mode and IO-Link
mode.
In SIO mode the static group behaves like an
actuator: the status of the HB alarm is available on
pin 5.
In IO-Link mode the static group communicates with
a standard IO-Link master on pin 5 of the push-in
connector.