81906_MAN_GRP-H_02-2022_ENG_pag. 24
4.1.3.5. Voltage reading scale maximum limit
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
H.tV
Inputs
VT line input
R
■
V
(*)
Voltage reading scale maximum limit.
(*)
Model
Default
480 V
560.0
600 V
690.0
4.1.3.6. Voltage reading input real-time value
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
I.tV
Expert
Status
Voltage
R
-
V
-
Voltage reading real-time value.
4.1.3.7. Voltage reading input value
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
I.tVF
Status
R
-
V
-
Filtered voltage reading value.
4.1.3.8. Mains voltage frequency
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
FrEq
Status
R
-
Hz
-
Mains voltage frequency.
4.1.3.9. Voltage reading status
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
STATUS3
Expert
Status
Diagnostics
R
-
-
-
Voltage reading self-diagnosis status.
Bit
Meaning
4
Frequency warning: frequency outside the 50Hz or 60Hz range
5
50Hz (0) / 60 Hz (1)