GE UFC 207 Owner'S Manual Download Page 8

8

Once the cap is removed, wipe the System Cap out with
a clean, soft cloth, remove the O-ring carefully, wipe the
O-ring with a clean cloth, check the O-ring for damage or
wear, apply a very small amount of DOW CORNING 111
silicone lubricant on the O-ring, and replace the O-ring. If
necessary, replace the O-ring with a new O-ring.

WARNING!

Disposable protective gloves must be worn during
maintenance of the System to protect your hands.
At the end of the procedure, wash your hands
thoroughly with soap and water. Do not reuse the
gloves. Dispose of the gloves in the garbage.

4

4

4

4

4

For Ground Water Systems, refer to Ground Water
Application Cleaning Procedures section before
beginning this step.

Vertical Systems:

With the Internal Prefilter still removed, pour 2 cups
(500 ml) of 5 - 6% unscented household chlorine bleach
OR 1 cup (250 ml)  of 12% chlorine bleach into the
Prefilter cavity.  Replace the System Cap. Slowly open the
Inlet Valve to pressurize the System. Let stand for 

60

minutes

.

 

3

 

3

 

3

 

3

 

3

Vertical Systems:

Remove the System Cap using the Cap Wrench. The
water level should be at least 2" above the Internal
Prefilter spigot.

If the water level is below 2”, open the Inlet Valve slowly
to raise the water level.

Close the Inlet and Outlet Valves. Using the

Controller, initiate a Manual Flush sequence to bring
System pressure to close to zero. Refer to the
instructions in the 

Controller Functions

 section under

 D.

OPERATIONS

 on how to perform a Manual Flush

sequence. 

Slowly open the Mini Ball Valve to ensure

there is no pressure in the System.  Water will flow out,
but should not spray.  Close the Mini Ball Valve
immediately.  If there is spray, repeat the Manual Flush
sequence.  Reinsert the Plug into the Mini Ball Valve.

2

2

2

2

2

1

1

1

1

1

Ensure that the two Mini Ball Valves are closed (To

close, turn the handle perpendicular to the Plug/hose
end). Remove the Plug from the Inlet Mini Ball Valve by
depressing the lock ring and pulling on the Plug.

Horizontally-mounted Systems: 

Ensure that there is still

some water inside the System after the Manual Flush. Do
not empty the System completely. If water stops coming
out during the Manual Flush, open the Inlet Valve slowly to
fill the System again.

System Membrane Cleaning

FIGURE 7

The following System cleaning procedures are
performed by the Homespring ™ Authorized Technician
during the annual maintenance.

The valve is OPEN when
handle is in the position
shown

 lock
 ring

 

FIGURE 6

Mini Ball
Valve

Do not use a bottle of bleach more than 3 months
old.

If a Bypass Valve is installed, the Bypass Valve
should be closed for the entire procedure to avoid
contaminated water entering the household
distribution system. Contaminated water might
cause personal injury and in some cases death.

This cleaning procedure does NOT disinfect the
household pipes. If potentially microbiologically
unsafe water is present in the pipes, it is strongly
recommended that all pipes be sanitized.

WARNING!

Summary of Contents for UFC 207

Page 1: ...Pages 13 to 14 H REPLACEMENT PART LIST AND PROCEDURES Pages 15 to 18 I SPECIFICATIONS Pages 19 to 20 J FAQ Pages 21 to 22 2006 V10 0 P N 23331 UFC 211 UFC 211 UFC 211 UFC 211 UFC 211 UF 211 UF 211 UF...

Page 2: ...dissertation on the principles set out above nor is it intended to be relied upon by anyone but Homespring Customer Care Consultants and Qualified Technicians Any other reliance is expressly excluded...

Page 3: ...do may result in System damage serious personal injury death and or property damage Use of non OEM parts will void the manufacturer s warranty The System is not intended for the treatment of water fro...

Page 4: ...nd Certified by NSF International against NSF ANSI 42 and 53 for Cyst Reduction Turbidity Reduction Particulate Reduction Class 1 System Tested and Certified by NSF International against NSF ANSI 42 a...

Page 5: ...even during a power failure Electricity is only required to activate the self cleaning sequences Normal Operation System Description Startup Information Sanitizing Information Setting the Controller...

Page 6: ...ect a Flush Drain Interval setting appropriate to the specific application Increase frequency of flush drain cycle if the System TMP rises too quickly Increasing the number of Flush Drain cycles per d...

Page 7: ...erform an Integrity Test to check the condition of the System membrane and perform a cleaning procedure to clean the System membrane This annual test and cleaning is mandatory as part of the 5 year li...

Page 8: ...ions in the Controller Functions section under D OPERATIONS on how to perform a Manual Flush sequence Slowly open the Mini Ball Valve to ensure there is no pressure in the System Water will flow out b...

Page 9: ...the flushing is complete open the Outlet Valve and a nearby COLD water tap to flush most of the chlorine from the System Run the tap fully open for at least 60 minutes Note Use only COLD water taps an...

Page 10: ...stall a new filter cartridge Re attach the filter housing to the head 2 2 2 2 2 Remove the drain hose and Nylon Elbow from the Drain Solenoid Valve and install a MNPT or MNPT PVC plug depending on the...

Page 11: ...eze water mix from the System into an empty container Add the remainder of the antifreeze into the Internal Prefilter cavity The fluid level in the System must be at least 2 above the bottom of the In...

Page 12: ...s If the System is on ground or well water the System must be cleaned with MC1 Cleaning Agent instead of chlorine bleach Follow the directions on the package for preparing the MC1 Cleaning Agent Never...

Page 13: ...ack cap on Air Relief Valve must be backed off by 1 5 turns from tight to allow air in and out of System Using the Controller initiate a manual flush sequence Refer to Controller Functions section und...

Page 14: ...ve Contact your Dealer to replace valve if necessary Inlet Solenoid Valve with Surface Water Option Kit Doesn t close to allow System to drain Does not open to allow flushing Check transformer is plug...

Page 15: ...may need to be washed or replaced prior to the Annual Maintenance A decrease in water pressure at the taps may indicate that the External Prefilter may need to be replaced Note For rinsing of the used...

Page 16: ...16 1 3 2 5 7 6 8 8 9 11 12 13 14 20 16 17 15 24 26 25 29 30 31 32 UFC 207 UF 207 UFC 209 UF 209 UFC 211 and UF 211 Series 18 FIGURE20 28 27 19 21 10 4 22 23...

Page 17: ...X 12 23154 System Cap Long X 13 23214 Loading O ring X X 14 23260 Kit Locking Clip with mounting screw X X 15 23159 System Base X X 16 23172 Thimble Filter X X 17 23221 Plug 1 4 NPT X X 18 23145 Serv...

Page 18: ...2 23090 External Prefilter O Ring X 3 23061 1 to Reducing Bushing X 4 23317 Inlet Solenoid Valve X 5 23054 Check Valve X 6 23137 Brass Closed Nipple X 7 23072 External Prefilter housing and head X 8...

Page 19: ...4 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres S y stem effic iency 87 94 92 96 94 97 Controller voltage 24 V A C 24 V A C 24 V A C Inlet port fem ale 3 4...

Page 20: ...ter use US gallons 15 gal 56 7 litres Program 3 2 flush backpulse cycles 1 drain cycle Estimated water use US gallons 13 5 gal 51 litres Program 4 2 flush backpulse cycles 2 drain cycles Estimated wat...

Page 21: ...the Carbon Prefilter are removed as the water passes from the outside of the Prefilter to the inside 2 The prefiltered water then passes down into the System to the membrane chamber 3 In the membrane...

Page 22: ...our water This includes calcium and magnesium which contribute to your hard water and other dissolved solids like essential minerals and flouride How long does the automatic cleaning cycle take Depend...

Page 23: ...23...

Reviews: