
7
At the start of the System’s 11
th
month of operation, the
yellow service indicator light will come on. This is an
indication that the System Annual Maintenance is
required.
At the System’s 11½
th
month of operation, the yellow
service indicator light will begin to flash and an audible
alarm will start to beep.
To temporarily silence the alarm, depress and hold the
UP and DOWN arrows
together
for three seconds. The
alarm will come back on in seven days after this
command is executed.
To permanently turn the alarm off, depress and hold the
UP and DOWN arrows
together
and press ENTER.
“A oF” (alarm off) will appear on the screen. To turn the
alarm on again, repeat the above step. “A on” (alarm on)
will appear on the screen.
The yellow service indicator light and the alarm can only
be reset by a Homespring Authorized Technician during
the Annual Maintenance.
A. Manual Flush
Note: For use when the instructions in this manual call for
a Manual Flush.
To manually flush the System, press NEXT once.
“MANUAL”
flashes on the screen. Press MANUAL
FLUSH to open the Drain Solenoid Valve. If the MANUAL
FLUSH button is held down for 5 seconds, the Drain
Solenoid Valve will remain open for 5 minutes. To
interrupt flushing, press MANUAL FLUSH again. The
Drain Solenoid Valve will be closed automatically after 5
minutes if not interrupted.
B. Light and Alarm Function:
The green light on the controller indicates that the
System is in operation. The green light will be on for 10
months from the first commissioning of the System.
WARNING!
The green light is NOT an indication of the integrity
of the membrane inside the System.
Controller Functions
A Homespring™ Authorized Technician must perform all
service and maintenance. As part of the annual
maintenance, the Homespring™ Authorized Technician
will perform an Integrity Test to check the condition of the
System membrane and perform a cleaning procedure to
clean the System membrane. This annual test and
cleaning is
mandatory
as part of the 5-year limited
prorated membrane warranty.
If the Homespring™ Authorized Technician determines
that the System has a high degree of debris and
contaminants, causing an abnormally high reduction in
System flowrate, the number of maintenance visits per
year may be increased to ensure that the System
functions within its acceptable operational parameters
and to ensure that the limited warranty remains in effect.
Maintenance Schedule
The following maintenance tasks must be performed
every 12 months unless specified otherwise. Refer to
H. REPLACEMENT PART LIST AND PROCEDURES
for part
numbers.
Every 6 Months:
For models equipped with the
Surface
Water Option Kit
, the External Prefilter cartridge must be
inspected, cleaned and/or replaced.
System Part
Annual Maintenance Tasks
UFC 207,
UFC 209,
UFC 211
UF 207,
UF 209,
UF 211
Carbon
Prefilter
Replace.
Water sources with high level of
particulate and/or chlorine will
require more frequent replacement.
X
n/a
Stainless
Steel Prefilter
Clean. Water sources with high
level of sediment will require more
frequent cleaning.
n/a
X
System
Membrane
Clean
X
X
System
Membrane
Perform Integrity Test
X
X
Backpulse
Tank Air
Pressure
Check and adjust
X
X
Controller
Batteries
(2-AA)
Replace
X
X
Controller
Flushing and
Draining
Programs
Verify if settings are still
appropriate.
X
X
E. MAINTENANCE SCHEDULE
WARNING!
The System has been designed and tested to offer
reliable service, provided if it is installed,
commissioned, operated, maintained and tested in
strict accordance to the safety instructions contained
in this manual. Failure to properly maintain the System
will compromise performance and/or result in a failure
to control water quality which may lead to delivery of
contaminated water. Consuming contaminated
water could result in serious injury or possibly death.
Summary of Contents for UFC 207
Page 23: ...23...