![GE PQM II Instruction Manual Download Page 96](http://html.mh-extra.com/html/ge/pqm-ii/pqm-ii_instruction-manual_128427096.webp)
5–12
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.2.8
Clear Data
PATH: SETPOINTS
Ö
S1 PQMII SETUP
ÖØ
CLEAR DATA
•
CLEAR ENERGY VALUES
: Enter “Yes” to clear all the energy used data in the
A1
METERING
ÖØ
ENERGY
actual values subgroup. The
TIME OF LAST RESET
date under
the same subgroup is updated upon issuing this command.
•
CLEAR MAX DEMAND VALUES
: Enter “Yes” to clear all the maximum power and
current demand data under the actual values subgroup
A1 METERING
ÖØ
DEMAND
.
The time and date associated with each message will be updated to the current date
upon issuing this command.
•
CLEAR ALL DEMAND VALUES
: Enter “Yes” to clear all the power and current demand
data under the actual values subgroup
A1 METERING
ÖØ
DEMAND
. The time and date
associated with each message will be updated to the current date upon issuing this
command.
•
CLEAR MIN/MAX CURRENT VALUES
: Enter “Yes” to clear all the minimum/maximum
current data under the actual values subgroup
A1 METERING
ÖØ
CURRENT
. The time
and date associated with each message will be updated to the current date upon
issuing this command.
•
CLEAR MIN/MAX VOLTAGE VALUES
: Enter “Yes” to clear all the minimum/maximum
voltage data under the actual values subgroup
A1 METERING
ÖØ
VOLTAGE
. The time
CLEAR DATA
[
Z
]
CLEAR ENERGY
VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MAX DEMAND
VALUES: NO
Range: Yes, No
MESSAGE
CLEAR ALL DEMAND
VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MIN/MAX
CURRENT VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MIN/MAX
VOLTAGE VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MIN/MAX
POWER VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MIN/MAX
FREQUENCY VALUES: NO
Range: Yes, No
MESSAGE
CLEAR MAX THD
VALUES: NO
Range: Yes, No
MESSAGE
CLEAR PULSE INPUT
VALUES: NO
Range: Yes, No
MESSAGE
CLEAR EVENT RECORD:
NO
Range: Yes, No
MESSAGE
CLEAR VOLTAGE DIST.
RECORD: NO
Range: Yes, No
MESSAGE
LOAD FACTORY DEFAULT
SETPOINTS: NO
Range: Yes, No
Summary of Contents for PQM II
Page 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Page 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Page 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Page 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Page 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Page 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...