![GE PQM II Instruction Manual Download Page 74](http://html.mh-extra.com/html/ge/pqm-ii/pqm-ii_instruction-manual_128427074.webp)
4–16
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 4: SOFTWARE
Z
Select the
Actual > Power Analysis > Trace Memory
menu item to
view the trace memory data.
This launches the Trace Memory Waveform window.
4.5.4
Data Logger
The data logger feature allows the PQMII to continuously log various specified parameters
at the specified rate. The data logger uses the 64 samples/cycle data. This feature is
implemented into EnerVista PQMII Setup Software as shown below.
Z
Select the
Setpoint > System Setup > Data Log
menu item to setup the
data logger feature.
This launches the Data Log settings box shown below. The state of each
data logger and percent filled is shown.
Z
Use the
Start Log 1(2)
and
Stop Log 1(2)
buttons to start and stop the
logs.