CHAPTER 6: MONITORING
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
6–11
Power metering actual values are displayed in this page. The
S1 PQMII SETUP
ÖØ
CLEAR DATA
ÖØ
CLEAR MIN/MAX POWER VALUES
setpoint can be used to clear the minimum and maximum
values.
FIGURE 6–1: Power Measurement Conventions
for the convention used to describe
power direction.
•
THREE PHASE/A/B/C REAL POWER
: The total RMS three phase real power as well as
individual phase A/B/C real power is displayed. The phase A/B/C real power messages
are displayed only for a “Wye” or “3 Wire Direct” connections. The PQMII shows
direction of flow by displaying the signed value of kW.
•
THREE PHASE/A/B/C REACTIVE POWER
: The total RMS three phase reactive power as
well as the individual phase A/B/C reactive power is displayed. The phase A/B/C
reactive power messages will be displayed only for a “Wye” or “3 Wire Direct”
connected system. The PQMII shows direction of flow by displaying the signed value of
kvar.
•
THREE PHASE/A/B/C APPARENT POWER
: The total RMS three phase apparent power
as well as the individual phase A/B/C apparent power is displayed. The phase A/B/C
apparent power messages will be displayed only for a “Wye” or “3 Wire Direct”
connected system.
•
THREE PHASE/A/B/C POWER FACTOR
: The three phase true power factor as well as
the individual phase A/B/C true power factors is displayed in these messages. The
phase A/B/C true power factor messages will be displayed only for a “Wye” or “3 Wire
Direct” connected system.
•
3
Φ
/A
Φ
/B
Φ
/C
Φ
kW MIN/MAX
: The minimum/maximum three phase real power as
well as the minimum/maximum individual phase A/B/C real power is displayed, along
with the time and date of their measurement. This information is stored in non-volatile
memory and will be retained during a loss of control power. The phase A/B/C
minimum/maximum real power messages will be displayed only for a “Wye”
connected system.
•
3
Φ
/A
Φ
/B
Φ
/C
Φ
kvar MIN/MAX
: The minimum/maximum three phase reactive power
as well as the minimum/maximum individual phase A/B/C reactive power is displayed,
along with the time and date of their measurement. This information is stored in non-
volatile memory and will be retained during a loss of control power. The phase A/B/C
minimum/maximum reactive power messages will be displayed only for a “Wye”
connected system.
MESSAGE
C
Φ
kVA MIN =
1007
12:00:00am
01/01/95
MESSAGE
C
Φ
PF MIN = 0.99 Lag
12:00:00am
01/01/95
MESSAGE
C
Φ
kW MAX =
1000
12:00:00am
01/01/95
MESSAGE
C
Φ
kvar MAX =
120
12:00:00am
01/01/95
MESSAGE
C
Φ
kVA MAX =
1007
12:00:00am
01/01/95
MESSAGE
C
Φ
PF MAX = 0.99 Lag
12:00:00am
01/01/95
Summary of Contents for PQM II
Page 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Page 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Page 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Page 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Page 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Page 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...