CHAPTER 4: SOFTWARE
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
4–15
running total of all valid Trace Memory Triggers from the last time power was applied to
the PQMII. The Total Trace Triggers counter will rollover to 0 at 65536. The trace memory
feature is implemented into the EnerVista PQMII Setup Software as shown below.
Z
Select the
Setpoint > PQMII Setup > Trace Memory Setup
menu
item to setup the trace memory feature.
The
Trace Memory Usage
parameter is set as follows:
• 1 x 36 cycles: upon trigger, the entire buffer is filled with 36 cycles of data
• 2 x 18 cycles: 2 separate 18-cycle buffers are created and each is filled upon a
trigger
• 3 x 12 cycles: 3 separate 12 cycle buffers are created and each is filled upon a
trigger
If the
Trace Memory Trigger Mode
is set to “One-Shot”, then the trace memory is triggered
once per buffer; if it is set to “Retrigger”, then it automatically retriggers and overwrites the
previous data.
The
Trace Memory Trigger Delay
delays the trigger by the number of cycles specified. The
Voltage, Current, and Switch Inputs selections are the parameters and levels that are used
to trigger the trace memory. Clicking
Save
sends the current settings to the PQMII.
Summary of Contents for PQM II
Page 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Page 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Page 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Page 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Page 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Page 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...