5–46
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.5.6
Demand Alarms
PATH: SETPOINTS
ÖØ
S4 ALARMS/CONTROL
ÖØ
DEMAND
•
PHASE A/B/C/NEUTRAL CURRENT DMD RELAY
: Phase/neutral current demand
detection can either be disabled or used as an alarm or process control. Set this
setpoint to “Off” if the feature is not required. Selecting “Alarm” activates the alarm
relay and displays an alarm message whenever a phase/neutral current demand level
DEMAND
[
Z
]
PHASE A CURRENT DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
PHASE A CURRENT DMD
LEVEL
≥
100
A
Range: 10 to 7500 A in steps of 1
MESSAGE
PHASE B CURRENT DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
PHASE B CURRENT DMD
LEVEL
≥
100
A
Range: 10 to 7500 A in steps of 1
MESSAGE
PHASE C CURRENT DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
PHASE C CURRENT DMD
LEVEL
≥
100
A
Range: 10 to 7500 A in steps of 1
MESSAGE
NEUTRAL CURRENT DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
NEUTRAL CURRENT DMD
LEVEL
≥
100
A
Range: 10 to 7500 A in steps of 1
MESSAGE
3
Φ
POS REAL PWR DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
3
Φ
POS REAL PWR DMD
LEVEL
≥
1000
kW
Range: 1 to 65000 kW in steps of 1
MESSAGE
3
Φ
POS REACT PWR DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
3
Φ
POS REACT PWR DMD
LEVEL
≥
1000
kvar
Range: 1 to 65000 kvar in steps of 1
MESSAGE
3
Φ
NEG REAL PWR DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
3
Φ
NEG REAL PWR DMD
LEVEL
≥
1000
kW
Range: 1 to 65000 kW in steps of 1
MESSAGE
3
Φ
NEG REACT PWR DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
3
Φ
NEG REACT PWR DMD
LEVEL
≥
1000
kvar
Range: 1 to 65000 kvar in steps of 1
MESSAGE
3
Φ
APPARENT PWR DMD
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
3
Φ
APPARENT PWR DMD
LEVEL
≥
1000
kVA
Range: 1 to 65000 kVA in steps of 1
Summary of Contents for PQM II
Page 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Page 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Page 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Page 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Page 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Page 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...