Index
GFK-2839B
PAC8000* IO PROFINET Scanner
User’s Manual–September 2017
45
Channel
Error
Type
Diagnosis Alarm
Type
Module
or
Channe
l Error
Cause
Fault Text
Recommendation
273
Channel Diagnosis
Appears/Disappears
Channel
Channel fault
Channel fault
Verify Channel fault
274
Channel Diagnosis
Appears/Disappears
Channel
Secondary data fault
Secondary data fault
Verify Secondary data fault
4096
Channel Diagnosis
Appears/Disappears
Module
Module is in fault state
Module Fault
Detected
Contact GE-IP support team
4097
Channel Diagnosis
Appears/Disappears
Module
Parameterization error
due to Configurator or
Corrupted GSDML file
used for configuration
Module fatal
parameterization error
Verify that Configuration tool
is working properly and
GSDML file is not modified or
corrupted.
4098
Channel Diagnosis
Appears/Disappears
Module
Module not in a position
to accept the
configuration.
Module rejected
configuration
Power cycle the module. If the
problem still persists may be
module replacement required.
4099
Channel Diagnosis
Appears/Disappears
Module
A fatal error reset
happened (when
PNS is configured to
automatically restart
after a fatal error)
Auto-Restart event
occurred
Contact GE-IP support team
4.2.3
Clearing Faults on PAC8000 Modules
The PAC8000 PROFINET Scanner clears alarms as soon as the underlying condition returns
to normal.