P50 Agile P253
6 Protection Functions
P253/EN M/C
6-17
2.5
Phase Overcurrent Protection (Motor Short Circuit Protection)
Phase current faults are faults where fault current flows between two or more phases of a three-phase
power system. The fault current may be between the phase conductors only or, between two or more
phase conductors and earth. There are three types of phase fault:
•
Line to Line (accounting for approximately 8% of all faults)
•
Line to Line to Earth (accounting for approximately 5% of all faults)
•
Line to Line to Line (accounting for approximately 2% of all faults)
Although not as common as earth faults (single line to earth), phase faults are typically more severe.
Faults between phases seldom occur because of the relatively large amount of insulation between
phase windings. As the stator windings are completely enclosed in earthed metal most faults involve
earth, which would then operate the earth fault protection. However, a fast operating overcurrent
element is often employed to protect against phase faults occurring at the motor terminals; such as
terminal flashovers.
2.5.1
Phase Overcurrent Protection Implementation
Phase Overcurrent Protection is implemented in the
OVERCURRENT
column of the relevant settings
group.
The product provides three stages of three-phase overcurrent protection with independent time delay
characteristics. All settings apply to all three phases but are independent for each of the three stages.
Stages 1, 2 and 3 provide a choice of operate and reset characteristics, where you can select
between:
•
A range of standard IDMT (Inverse Definite Minimum Time) curves
•
DT (Definite Time)
This is achieved using the cells
•
I>
(n)
Function
for the overcurrent operate characteristic
•
I>
(n)
Reset Char
for the overcurrent reset characteristic
where (n) is the number of the stage.
The IDMT-capable stages, (1, 2 and 3) also provide a Timer Hold facility.This is configured using the
cells
I>
(n)
tRESET
, where (n) is the number of the stage. Timer Hold facility is applicable for both IEC
and IEEE curves. IEEE & US curves have IDMT reset curve option in addition to DT Phase
Overcurrent protection logic.
Phase Overcurrent modules are level detectors that detect when the current magnitude exceeds a set
threshold. When this happens, the Phase Overcurrent module in question issues a signal to produce
the
Start
signal. This
Start
signal is applied to the IDMT/DT timer module. It is also made available
directly to the user for use in the logic functions.
There are three Phase Overcurrent Modules, one for each phase. The three
Start
signals from each
of these phases and common
Start
signal for each stage of phase overcurrent function is available for
customer use.
The outputs of the IDMT/DT timer modules are the trip signals which are used to drive the tripping
output relay. The three
Trip
signals from each of the phases and common
Trip
signal for each stage
of phase overcurrent function is available for customer use.
The Phase overcurrent trip signal can be blocked by:
•
The Second Harmonic blocking function which is for all three phases. The blocking is
activated by setting the
I>(n) 2H Blocking
cell to ‘Enabled’, where (n) is the number of the
stage.
Summary of Contents for P50 Agile P253
Page 3: ...P50 Agile P253 1 Introduction P253 EN M C 1 1 INTRODUCTION CHAPTER 1 ...
Page 4: ...1 Introduction P50 Agile P253 1 2 P253 EN M C ...
Page 11: ...SAFETY INFORMATION CHAPTER 2 ...
Page 12: ...Safety Information Pxxx 2 ...
Page 23: ...P50 Agile P253 3 Hardware Design P253 EN M C 3 1 HARDWARE DESIGN CHAPTER 3 ...
Page 24: ...3 Hardware Design P50 Agile P253253 3 2 P253 EN M C ...
Page 28: ...3 Hardware Design P50 Agile P253253 3 6 P253 EN M C E00276 Figure 2 Hardware design overview ...
Page 32: ...3 Hardware Design P50 Agile P253253 3 10 P253 EN M C ...
Page 33: ...P50 Agile P253 4 Front Panel P253 EN M C 4 1 FRONT PANEL CHAPTER 4 ...
Page 34: ...4 Front Panel P50 Agile P253 4 2 P253 EN M C ...
Page 39: ...P50 Agile P253 4 Front Panel P253 EN M C 4 7 Figure 2 USB port ...
Page 40: ...4 Front Panel P50 Agile P253 4 8 P253 EN M C ...
Page 41: ...P50 Agile P253 5 Configuration P253 EN M C 5 1 CONFIGURATION CHAPTER 5 ...
Page 42: ...5 Configuration P50 Agile P253 5 2 P253 EN M C ...
Page 154: ...5 Configuration P50 Agile P253 5 114 P253 EN M C ...
Page 155: ...P50 Agile P253 6 Protection Functions P253 EN M C 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Page 156: ...6 Protection Functions P50 Agile P253 6 2 P253 EN M C ...
Page 182: ...7 Protection Parameter Settings P50 Agile P253 7 2 P253 EN M C ...
Page 203: ...P50 Agile P253 8 Monitoring Control P253 EN M C 8 1 MONITORING CONTROL CHAPTER 8 ...
Page 204: ...8 Monitoring Control P50 Agile P253 8 2 P253 EN M C ...
Page 222: ...8 Monitoring Control P50 Agile P253 8 20 P253 EN M C ...
Page 223: ...P50 Agile P253 9 SCADA Communications P253 EN M C 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Page 224: ...9 SCADA Communications P50 Agile P253 9 2 P253 EN M C ...
Page 249: ...P50 Agile P253 10 Installation P253 EN M C 10 1 INSTALLATION CHAPTER 10 ...
Page 250: ...10 Installation P50 Agile P253 10 2 P253 EN M C ...
Page 260: ...11 Commissioning Instructions P50 Agile P253 11 2 P253 EN M C ...
Page 270: ...11 Commissioning Instructions P50 Agile P253 11 12 P253 EN M C ...
Page 272: ...12 Maintenance and Troubleshooting P50 Agile P253 12 2 P253 EN M C ...
Page 282: ...13 Technical Specifications P50 Agile P253 13 2 P253 EN M C ...
Page 292: ...13 Technical Specifications P50 Agile P253 13 12 P253 EN M C ...
Page 293: ...P50 Agile P253 14 Wiring Diagrams P253 EN M C 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Page 294: ...14 Wiring Diagrams P50 Agile P253 14 2 P253 EN M C ...
Page 297: ......