NX-1710E Single Door Control
7
V.
ADDRESSING
The first thing that must be decided is the address of this particular relay/output module. This is the address that
will be selected when programming the auxiliary devices. To set the addresses use the table below. Refer to
Table V-1 that follows for possible addresses.
The door control unit must be powered down and powered back up in order to read
new or modified dip switch settings.
Table V-1
Bus Address
Dip Switch Setting
Bus Address
Dip Switch Setting
1
2
3
4
1
2
3
4
128
136
ON
129
ON
137
ON
ON
130
ON
138
ON
ON
131
ON
ON
139
ON
ON
ON
132
ON
140
ON
ON
133 ON
ON
141
ON
ON
ON
134
ON
ON
142
ON
ON
ON
135 ON
ON
ON
143
ON
ON
ON
ON
VI.
PROGRAMMING
USING THE LED KEYPAD
E
NTERING THE
P
ROGRAM
M
ODE
Enters the Program Mode.
Stay, Chime, Exit, Bypass & Cancel LEDS
will flash.
[
Go To Program Code
]
Factory Default is
If the "Go To Program Code" is valid, the
"Service" LED will flash and the five function
LEDs will illuminate steady. You are now in the
Program Mode and ready to select the module
address.
E
NTERING THE
M
ODULE
A
DDRESS
Scan a card.
#
(example only)
Enter the module address. Refer to Table V-1
for the address.
The Armed LED will illuminate while it is
waiting for a programming location to be
entered.
L
OADING THE
F
ACTORY
D
EFAULTS
(
USER PROGRAMMING ONLY
)
#
The keypad will beep 3 times indicating that
the loading is in progress. The loading takes
about 6 seconds.
D
EFAULTING THE
C
ARD
S
ERIAL
N
UMBERS
#
The keypad will beep 3 times indicating that
the loading is in progress.