8.1 SYMPTOMS AND RECOMMENDED ACTIONS
8 F650TROUBLESHOOTING GUIDE
8
Firmware
During the upgrading
procces for models
with IEC 61850
sometimes it ask for
password and
sometimes not.
-
Communication problems during the
upgrade procecure.
-
The procedure has been not
performed in a continuous way.
•
EnerVista 650 Setup program do not
ask for a password if the relay model is
IEC61850 and the procedure is
completed.
•
If during the process there is any
problem and has to be started again,
this second time the program will ask
to confirm the IEC password.
•
If the EnerVista 650 Setup program
is closed and started again during the
bootware and firmware upgrade
process, the program will ask to
confirm the IEC password.
Firmware
Password for
IEC61850 incorrect
- Model change
- Incorrect mac or serial number
•
The password is tied to the model,
MAC Address and serial number, any
change in any of the following will need
a password change.
•
If the model has been modified to
add or replace any boards or
communication protocol, the IEC
61850 passwords will need to be
updated (contact the factory).
EnerVista 650 Setup
InstallShield Setup
Initialization Error
6001
A previous installation of any product
using InstallShield for installation may
have corrupted some of the
InstallShield files used in the EnerVista
650 Setup installation
Delete (or rename) the 0701 folder
located in "C:\Program Files\Common
Files\InstallShield\Professional\RunTi
me\" and retry installation
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...