3.2 HUMAN MACHINE INTERFACE (HMI)
3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
3
3.2.2 FRONT LED INDICATORS
The relay provides 16 LED indicators, 15 user programmable plus one non-configurable LED (READY) that shows if the
relay is in service.
Programmable LEDs are divided into groups of 5 LEDs, each of the groups having a different color. The first group of LED
indicators is latched by hardware (red color ones), usually configured for trip signals. The second group (yellow color) and
third group (green color) of LED indicators are self-reset type and will be reset once the condition has been cleared, but can
be latched using logic through PLC configuration.
The ESC key is used to reset any latched led indicator, once the condition has been cleared. Keep the ESC button pressed
for more than 3 seconds; all LEDs will light up, verifying their correct operation. When releasing the ESC key, all indicators
programmed with memory, such as tripping LEDs, will be reset.
The latched conditions can also be reset via communications using the LED reset input (to configure this signal go to
“
Setpoint>Relay Configuration>Protection elements>LED RESET INPUT
”). By default this LED reset input signal is set
to LEDS RESET operation.
3.2.3 PUSHBUTTONS
The front panel provides:
Push buttons:
keypad (5 user programmable plus ESC non configurable), shuttle key or shuttle key for easy navigation,
command pushbutton to select operations mode.
RS232 port
: intended for connection to a portable PC.
3.2.3.1 KEYPAD AND SHUTTLE KEY
Figure 3–15: KEYPAD AND SHUTTLE KEY DESCRIPTION
This button can be used for closing the user programmable switchgear. It is fully
programmable by the user.
This button can be used for closing the user programmable switchgear. It is fully
programmable by the user.
User programmable.
User programmable.
User programmable.
(ESC) Escape key. When pressed during more than 3 seconds, it will test all LEDs and
reset the trip LEDs.
Rotary knob or Shuttle Key (it can be both rotated and pressed): Used for selecting
menus, submenus, settings and for confirmation. Press or rotate the shuttle key to enter
the text main menu from the text standby screen.
O
*
F1
I
F2
ESC
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...