GEK-113000AE
F650 Digital Bay Controller
D-13
APPENDIX D
D.1 FACTORY DEFAULT SETTINGS
D
SETPOINT > PRODUCT SETUP > TIME SETTINGS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Local time zone offset Universal
Coodinated Time
LOC. TIME OFFS.
UTC
0
1
[-24,0 : 24,0]
To follow DST rules
DAYLIG. SAVINGS
TIME
DISABLED
NA
[DISBLED; ENABLED]
Set the start month of the DST
DST START
MONTH
MAR
MONTH
January to December
Set the start weekday of the DST
DST START
WEEKDAY
SUNDAY
DAY
Monday to Sunday
Set the start day instance
DST START DAY
INST
LAST
NA
First; Second; Third;
Fourth; Last
Set the starting hour of the DST
DST START HOUR
2
1
[0 : 23]
Set the Stop month of the DST
DST STOP MONTH
OCT
Month
January to December
Set the stop weekday of the DST
DST STOP
WEEKDAY
SUNDAY
Day
Monday to Sunday
Set the stop day instance
DST STOP DAY
INST
LAST
NA
First; Second; Third;
Fourth; Last
Set the stop hour of the DST
DST STOP HOUR
2
1
[0 : 23]
IRIG-B local time
IRIG-B LOCAL TIME
OFF
NA
[ON; OFF]
Function permission
IRIGB Function
DISABLED
NA
ENABLLED; DISABLED
Stablish the sync priority
PTP IRIGB Priority
PTP-1588
NA
PTP-1588; IRIG_B
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Phase CT ratio
Phase CT Ratio
1.0
0.1
[1.0 : 6000.0]
Ground CT ratio
Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Sensitive ground CT ratio
Stv Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Phase VT ratio
Phase VT Ratio
1.0
0.1
[1.0 : 6000.0]
Phase VT connection
Phase VT Connection WYE
N/A
[WYE – DELTA]
Rated voltage
Nominal Voltage
100.0
0.1
[1.0 : 250.0]
Rated Frequency
Nominal Frequency
50 Hz
Hz
[50-60]
Phase rotation
Phase Rotation
ABC
N/A
[ABC – ACB]
Frequency reference
Frequency Reference VI
N/A
[VI-VII-VIII]
Auxiliary Voltage
Auxiliary Voltage
VX
N/A
[VX – VN]
Snapshot Event generation
Snapshot Events
DISABLED
N/A
[DISABLED – ENABLED]
Primary meter units
Primary meter units
kA_kV
NA
A_V; kA_kV
Device name
Device name
NA
NA
NA
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Values for reset points 0.00 pkp
Time 0.00xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.05 pkp
Time 0.05xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
…
…
…
0.001 s
[0.000 : 65.535]
Values for reset points 0.97 pkp
Time 0.97xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.98 pkp
Time 0.98xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for operation points 1.03 pkp
Time 1.03xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
Summary of Contents for Multilin F650
Page 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Page 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Page 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Page 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Page 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Page 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...