05-4801A01, Rev. A
MDS NETio-TB Installation & Operation Guide
77
• Current Draw
• Transmit: less than 600 mA (@13.8V)
• Receive: less than 100 mA (@13.8V)
• Sleep Mode: 10mA at 12 Vdc less than 1mA at 12 Vdc in
Shutdown Mode
• Temperature: -40 to +70 degrees C
NETio Base Module
• NETio-TB:
• I/O Capacity: 1 AI, 1 AO, 2 DI, 2 DO
+ AI Type: Configurable as 4-20mA, 0-5 Vdc, 0-10 Vdc
+ AO Type: 4-20 mA
• Supports serial communication
• Compatible with MDS TransNET Masters
• Supports I/O Signal Extender functions or over WeXP to
wireless expansion modules
• Two serial RJ45 connectors, one separate device
NETio Expansion Module Models
• NETio-XM1 capacity: 1 AI, 1 AO, 2 DI, 2 DO
• AI Type: Configurable as 4-20mA, 0-5 Vdc, 0-10 Vdc
• AO Type: 4-20mA
• NETio-XM2 capacity: 6 DI
• NETio-XM3 capacity: 6 DO
• NETio-XM4 capacity: 2 AI, 4 DI
• AI Type: Configurable as 4-20mA, 0-5 Vdc, 0-10 Vdc
• NETio-XM6 capacity: 2 AI, 2 AO, 2 DI, 2 DO
• AI Type: 0-5 Vdc
• AO Type: 0-5 Vdc
• NETio-XM7 capacity: 2 AI, 1 DI, 3 DO
• AI Type: 4-20mA
Analog Input
• Optionally power 4-20 mA loop.
• Accuracy
• Current: ± 12.2 uA
• Voltage: ± 6.1 mV
• A/D Resolution: 22 bit
• Isolation: 1400 V input to power
• Note that inputs on XM6 are
not
isolated
Digital Inputs
• Type: 5-36 Vdc with pulse counting
• Isolation: 3000 V to chassis ground
RSPSupply - 1-888-532-2706 - www.RSPSupply.com