05-4801A01, Rev. A
MDS NETio-TB Installation & Operation Guide
39
High (1)
—Force Mode enabled and output is turned on.
Low (0)
—Force Mode enabled and output is turned off.
•
Force Value
—The value (in counts) to output when in Force
Mode.
•
Failsafe Timeout
—Amount of time (in ms) that the communi-
cation link with a Source Point must be lost before entering
Failsafe Mode.
Read-Only Parameters:
•
Point Address
—Address used to identify this input point. For-
mat is: Module ID, Point Number
•
Value
—The present value
in A/D counts for this point
address.
3.3 CONFIGURING NETio OUTPUTS
for PROTOCOL CONTROL
In order for a protocol to set control outputs for either analog or discrete
outputs connected to NETio Modules, the
Source
variable for the partic-
ular output must be set to
Protocol
. To do this, Select the letter for the
“Source” variable (shown in
Figure 3-5
or
Figure 3-6
) to view the menu
shown in
Figure 3-7
. Enter
p
to enable protocol control as the source for
the output.
Invisible place holder
Figure 3-7. I/O Mapping Wizard
3.4 MAPPING INPUTS TO OUTPUTS
FOR SIGNAL EXTENSION AND
REGENERATION
One of the primary uses of NETio is to regenerate Input signals con-
nected to NETio modules at one location as outputs from NETio mod-
ules at a
different
location. This is accomplished by mapping.