3.2.4 Discrete Output Menu
This menu allows you to view and change various parameters for a dis-
crete output point.
Figure 3-5. Discrete Output Menu
User-Alterable Parameters:
•
Point ID Tag
—Text to describe the use of this I/O point.
•
Source
—The input point address to get this output's value
from. Format is: Module ID, Point Number (see
Section
3.4
).
•
Force Mode
—A convenience field that allows the user to force
an output value. Press the spacebar to cycle through the avail-
able settings as follows:
Off
—Force Mode disabled.
High (1)
—Force Mode enabled and output is turned on.
Low (0)
—Force Mode enabled and output is turned off.
•
Failsafe Mode
—The way this output should fail if communica-
tions is lost. Press the spacebar to cycle through the options
as follows:
On
—On or logic 1.
Off
—Off or logic 0.
Last
—Hold last value
•
Failsafe Timeout
—Amount of time (in ms) that the communi-
cation link with a Source Point must be lost before entering
Failsafe Mode.
Read-Only Parameters:
•
Point Address
—Address used to identify this input point. For-
mat is: [
Module ID, Point Number
]
•
Value
—The current state (logic high or logic low) of this
point.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com