Chapter 5. Diagnostics
46
PACSystems RX3i Genius Communications Gateway
GFK-2892F
Fault Types Reported to the RX3i Controller I/O Fault Table
When imported into the Rx3i I/O Fault Table, the following Error Codes are displayed without explanation. The
following table is provided to assist in decoding the displayed error codes.
Fault Type
Description
257
Internal Circuit fault
258
Shared RAM fault
259
Electronics Assembly EEPROM fault
260
Communication interface fault
261
Terminal Strip EEPROM fault or NVRAM fault
262
EEPROM fault
263
Private RAM fault
264
Processor fault
273
Failed Switch
274
Open Input / Over-Temperature
275
No Load Present
276
Overload
277
Short Circuit
278
Loss of I/O Power
289
Feedback Error
290
Output channel over-range
291
Output channel under-range
292
Input channel open wire
293
Input channel over-range
294
Input channel under-range
295
Input channel high alarm
296
Input channel low alarm
305
Input channel shorted
306
Internal channel fault
307
Input channel wiring error
308
Input channel open wire
309
Input channel over-range
310
Input channel under-range
311
Input channel high alarm
312
Input channel low alarm
400
unknown Error-Type
513
Field Control, VersaMax or S90-70 Remote Scanner I/O fault
769
S90-70 Remote Scanner I/O fault
1026
Invalid Genius Gateway module configuration
1027
Invalid Genius Gateway module configuration
1028
Extra Genius device
1029
Configuration mismatch in S90-70 Remote Scanner Rack
1030
Configuration mismatch in VersaMax I/O Station
1031
Configuration mismatch in Field Control I/O Station
1032
Mismatch between configured Genius device and actual device present.
1033
Genius device is present on the bus, but is not in the configuration.
Figure 27 - I/O Fault Table Message Identifiers