Chapter 6. COMMREQ/Data_Init_Comm Programming
54
PACSystems RX3i Genius Communications Gateway
GFK-2892F
COMMREQ Command Block Quick Reference
The table below summarizes all COMMREQs supported by the Genius Gateway. Beyond
8
, please see
the individual COMMREQ specification in Sections 6.4.1 thru 6.4.18.
COMMREQ
COMMREQ Content
Addr
Addr+1
Addr+2
Addr+3
Addr+4
Addr+5
Addr+6
Addr+7
Addr+8
Length
Wait/
No Wait
Status
Pointer
Memory
Type
Status
Pointer
Offset
Idle
Timeout
Value
Max.
Comm
Time
COMM
REQ #
PROFINET
Device
Number
Genius
Device
Number
Pulse Test
3
0
0
0
1
1-255
0-31
Read
Configuration
7
0
0
0
2
1-255
0-31
Write
Configuration
4+n
0
0
0
3
1-255
0-31
Read
Diagnostics
7
0
0
0
4
1-255
0-31
Clear Circuit
Fault
4
0
0
0
5
1-255
0-31
Clear All
Circuit Faults
3
0
0
0
6
1-255
0-31,
255
Assign
Monitor
4
0
0
0
7
1-255
0-31
Outputs
Enable
/Disable
4
0
see 6.3.1
0
0
8
1-255
0-31,
255
Switch BSM
4
0
see 6.3.1
0
0
10
1-255
0-31
Read Device
18
0
0
0
11
1-255
0-31
Write Device
14-78
0
0
0
12
1-255
0-31
Read
Identification
7
0
0
0
19
1-255
0-31
Write Point
8
0
0
0
20
1-255
0-31
Read Block
I/O
8
0
0
0
21
1-255
0-31
Read Map
7
0
0
0
22
1-255
0-31
Write Map
12
0
0
0
23
1-255
0-31
Read Data
9
0
0
0
24
1-255
0-31
Write Data
7
0
0
0
25
1-255
0-31