Chapter 2. Installation
18
PACSystems RX3i Genius Communications Gateway
GFK-2892F
2.3
Installation in Hazardous Areas
The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for
explosive atmospheres:
CLASS 1 DIVISION 2 GROUPS ABCD
•
This equipment is an open-type device and is meant to be installed in an enclosure
suitable for the environment that is only accessible with the use of a tool.
•
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or
nonhazardous locations only.
Warning
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES; AND
DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS
POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO
BE NONHAZARDOUS.
Warning
EXPLOSION HAZARD - USB PORT IS ONLY FOR USE IN
NONHAZARDOUS LOCATIONS, DO NOT USE UNLESS AREA IS
KNOWN TO BE NON-HAZARDOUS.
ATEX Zone 2
The module must be mounted in an enclosure certified in accordance with EN60079-15 for use in Zone 2,
Group IIC and rated IP54. The enclosure shall only be able to be opened with the use of a tool.
ATEX Marking
II 3 G Ex nA IIC T4 X Ta: 0 - 60C