Control Circuit Wiring
Drive
IS
wired at shipment for operation and frequency
setting through the keypad panel (frequency is set at 60
Hz.)
See Figure
4-4 for wiring
See TABLE 4 for
of all
Make
connections as shown
Figure 4-4 through 4-6
for desired mode of external
through control
circuit
CAUTION:
The control
should be
kept as far away as possible from the
power
to
prevent operational error due to noise interference N e v e r
install both types of wiring
the same duct or conduit (A
separation distance of 4 inches
or more
IS
recommended.) If the control circuit wiring must cross the
main power wiring, it should cross at a right angle.
CAUTION.
Use shielded or twisted
for the control
circuit wiring (wiring should be as short as
65
feet or less
meters.]) Connect outer covering of the
shielded wires to the Drive ground terminal and leave the
other end open, but taped with electrical insulating tape.
D C R E L A Y
A C C O N T A C T O R
Figure 4-2
CAUTION:
Install a supressor
parallel with any relays
or
type
as shown above, that may
the
to prevent
from causing
4-2