Chapter 3: Programming
154
EST iO64 and iO500 Technical Reference Manual
Unconfigured alarm programming
The unconfigured alarm event can be assigned to a correlation
group and turn on an output device. When the unconfigured alarm
is assigned to a correlation group every output device in the
correlation group turns on. Event notification can also be
programmed for the unconfigured alarm.
Reports
Test
Control
Program
⇩
Program
Incremental Program
Auto Program
Advanced Program
⇩
Enter Password
0000
⇩
Advanced Program
Loop Events
Unconfigured Alarms
Common Trouble
⇩
Unconfigured Alarms
Loop 1 Unconf Alarm
Loop 2 Unconf Alarm
⇩
Correlation Groups
Group 01 Yes<>
Group 02 No<>
Group 03 No<>
⇩
Correlation Groups
Group 31 No<>
Group 32 No<>
Save
⇩
Unconfigured Alarm
Correlation Groups
Event Notification
To program the unconfigured alarm:
1. Press the Menu button.
2. Choose
Program.
3. Choose Advanced Program.
4. Enter the level two password.
5. Choose Advanced Program.
6. Choose
Unconfigured
Alarms.
7. Choose Loop 1 Unconf Alarm or Loop 2 Unconf Alarm (displayed
if you have more than one loop).
8. Choose Correlation Groups.
9. Choose a correlation group (1 to 32).
10. Select Yes to add the unconfigured alarm to the correlation
group or No to not add the unconfigured alarm to the
correlation group.
11. Repeat steps 8 and 9 until the unconfigured alarm is added or
removed from each correlation group needed.
12. Choose Save.
13. Choose Event Notification.
14. Choose Active.
15. Set active event notification.
Printer: Yes or No - Specifies if event information is printed
Coder: 4-digit coded output, which is played in response to
alarm conditions (00-00-00-00 to 99-99-99-99)
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
⇩