Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual
137
CMS device programming
CMS devices are your central monitoring station devices, which
include the dialer and network. These are the devices that transmit
system events to a central monitoring station's receiver.
CMS device programming
Dialer See
"Dialer
programming."
Network
See "Network programming."
Swinger shutdown
Set swinger shutdown to Off or 1 to 255 repetitions. When finished, press Enter to save. Note:
Off is the only acceptable setting for UL/ULC installations. Refer to "UL 864 programming
requirements" for details.
This automatically inhibits the number of consecutive times a single trouble event is
transmitted over a 24-hour period before it is no longer sent. Some trouble events are
not
affected when swinger shutdown is set. They are:
- Loop 1 initializing
- Loop 1 uncfgrd alarm
- Loop 1 map mismatch
- Loop 1 over limits
- Loop 1 device 000
- Loop 1 mapping
- Loop 1 map fault
- Loop 2 initializing
- Loop 2 map mismatch
- Loop 2 over limits
- Loop 2 device 000
- Loop 2 mapping
- Loop 2 map fault
- System startup
- Reset
- Reset/Sil inhibit
- Panel silence
- Program mode
- Signal silence
- Date
- Drill
- Walk test
- Test fire
- Time
- Clear history
- Common alarm
- Common disable
- Common monitor
- Common supervisory
- Common trouble
- Battery charger
- Battery low
- Battery missing
- Local AC power
- System wide AC power
- Self test fault
- Dialer dsbl/rem disc
- Dialer normal test
- Dialer abnormal test
- Dialer configuration