Chapter 3: Programming
148
EST iO64 and iO500 Technical Reference Manual
display, LEDs, printer, and dialer. Note: Device level reporting configuration is not available.
Zone/device: Zone information is sent to the LCD display and LEDs. Device information is sent
to the printer and dialer. Note: Zone/device reporting locations can be configured through
custom programming.
Device: Only device information is reported, no zone information.
LED annunciator operation note:
If you are using the optional LED expanders, the zone LEDs
are assigned to device addresses 1 to 32 on loop 1. For example, zone 1 LEDs (red and yellow)
are assigned to device 1 on loop 1.
Remote annunciator operation note:
If you are using the optional remote annunciators, when
an event takes place on loop 1, the loop displays on the annunciator LCD as loop 17 (not loop
1). The device number of the device reporting the event is the correct device number. So, if an
event takes place on loop 1, the remote annunciators will display it as loop 17. Loop 2 events
will display on the annunciator LCD as loop 2 events.
Key #1
Set to:
Enabled: Allows key 1 to perform its programmed function
Disabled: Disables key 1
Refer to "Programming the programmable keys" for more information.
Key #2
Set to:
Enabled: Allows key 2 to perform its programmed function
Disabled: Disables key 2
Refer to "Programming the programmable keys" for more information.
Reports
Test
Control
Program
⇩
Program
Incremental Program
Auto Program
Advanced Program
⇩
Enter Password
0000
⇩
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
⇩
To program the panel operation options:
1. Press the Menu button.
2. Choose
Program.
3. Choose Advanced Program.
4. Enter the level two password.
5. Choose
Panel
Operation.
6. Program the options using the "Panel operation programming
options" table above.
7. When you finish programming each option, choose Save.
8. Continue programming your system or press Menu to exit menu
mode.
Panel Operation
Language English>
Marketplace US>
AC Fail Delay 15>