Viewing and updating circuit breaker accessories
57
13
To view or change the circuit breaker accessories
1.
On the
Main Menu
, click the
Maintenance
button. The button will only be displayed if access
is allowed with the current login permissions.
2.
Click the
Accessories
tab. A table will display as shown as in Figure 13-2.
Figure 13-2
Breaker Accessories screen
•
Breaker Name
: Unique name given to a circuit breaker.
•
Electric Operated
: Accessory allows the circuit breaker to be opened, closed, and charged
remotely. The check box should be selected if this accessory is present.
•
LockOut
: Circuit breaker contains either a bell alarm lockout accessory to prevent reclosing
after tripping, or a network interlock accessory to prevent closing during automatic throw
over. The check box should be selected if this accessory is present.
•
Position Switch
: Circuit breaker contains an accessory that provides remote monitoring of
the position of the circuit breaker during rack-in and rack-out. The check box should be
selected if this accessory is present.
3.
Click the
Save
button to keep changes (or click
Cancel
to exit the screen without saving).
Summary of Contents for Entellisys DEH-230
Page 1: ...GE Entellisys Low Voltage Switchgear System Administrator Manual ...
Page 4: ......
Page 8: ...System administrator roles and responsibilities 8 1 ...
Page 10: ...Pre programming settings prior to switchgear arrival 10 2 2 ...
Page 12: ...Commissioning the switchgear 12 3 ...
Page 20: ...Time synchronization 20 5 ...
Page 28: ...Installing and configuring remote HMI software 28 7 ...
Page 32: ...Settings files and offline system configuration 32 8 Figure 8 3 Settings file compare screen ...
Page 40: ...System archives 40 10 ...
Page 44: ...Feature options 44 11 ...
Page 54: ...Preparing and configuring a replacement CPU 54 12 ...
Page 60: ...Other maintenance functions 60 13 ...
Page 62: ......