Other maintenance functions
56
13
•
Compartment#
: Unique identifier for the location of the circuit breaker in the switchgear.
The Compartment# is set by the factory upon shipment to the customer and cannot be
changed. It is often included on nameplates on the switchgear.
3.
Click the
Save
button to keep changes (or click
Cancel
to exit the screen without saving).
NOTE:
Changes to circuit breaker names will not be reflected on the custom Oneline screen.
Contact GE Post Sales Support for details about updating to the Oneline screen (see
How to
contact us on page 2
).
13.2 Viewing and updating circuit breaker accessories
The HMI displays the circuit breaker status for each circuit breaker in the system. To display the
proper circuit breaker status, the installed accessories must be known.
The following is affected by the installed accessories:
•
Breaker Racking Position status is available only if the position switch accessory is installed.
•
Electrically Locked Out status is available only if either the Bell-Alarm or Network Interlock
accessory is present.
•
Closing Spring Status is available only if the Electric Operated accessory is present.
Additionally, the Breaker Control relies on the electric operated circuit breaker accessory. The
remote control functions will be limited by the presence of the electrically operated accessory.
The following functions in the HMI Breaker Control are affected:
•
Open Breaker function is displayed only if the electrical operated accessory is present.
•
Close Breaker function is displayed only if the electrical operated accessory is present.
•
Trip Breaker is NOT affected.
GE configures the proper circuit breaker accessories upon shipment of the switchgear. However,
if the accessories change or if different circuit breakers are exchanged, the accessories must be
updated, otherwise the status might not be correct.
Summary of Contents for Entellisys DEH-230
Page 1: ...GE Entellisys Low Voltage Switchgear System Administrator Manual ...
Page 4: ......
Page 8: ...System administrator roles and responsibilities 8 1 ...
Page 10: ...Pre programming settings prior to switchgear arrival 10 2 2 ...
Page 12: ...Commissioning the switchgear 12 3 ...
Page 20: ...Time synchronization 20 5 ...
Page 28: ...Installing and configuring remote HMI software 28 7 ...
Page 32: ...Settings files and offline system configuration 32 8 Figure 8 3 Settings file compare screen ...
Page 40: ...System archives 40 10 ...
Page 44: ...Feature options 44 11 ...
Page 54: ...Preparing and configuring a replacement CPU 54 12 ...
Page 60: ...Other maintenance functions 60 13 ...
Page 62: ......