21
EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Figure 8D. AKD-10—Using eye bolts, chain and connector.
8.
Check that the breaker is free from obstruction inside the compartment.
9.
When the breaker is lined up with the compartment, raise the breaker only slightly higher than the
compartment floor.
10.
Keep the breaker steady. Continue to guide the breaker, while checking both sides and underneath, so
that both sets of rollers are lined up with the rails.
11.
Once the breaker is resting on the rails, unhook the lifting hooks from the circuit breaker. Move the
hoisting apparatus out of the way.
12.
Push the breaker in until the compartment racking pins engage with the breaker racking cams.