EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Neutral CT Adapter 150A-5000A
This is a miniature Rogowski coil. It mounts between the incoming Neutral CT and the breaker trip unit. It
converts the signal from an iron Core Neutral sensor to a Rogowski voltage output which is wired to the
Breaker's Trip Unit Neutral input connections.
The Neutral CT Adapter supports iron core Neutral sensors compatible with MicroVersa Trip, MVT RMS-9,
Power Plus, Pro Trip and EntelliGuard TU rated from 150 to 5000Amps as used in GE switchboards and
switchgear. It is available in five variations (shown in below Table).
Catalog Number
Supported Neutral CT ratings (A)
RNCTA1200 (R)
600, 1200
RNCTA2000 (R)
150, 200, 400, 800, 1000, 1600, 2000
RNCTA3000 (R)
3000
RNCTA4000 (R)
2500, 3200, 4000
RNCTA5000 (R)
5000
AKD-10—Rogowski Assemblies, Mechanical Views
Figure 25
shows a typical Rogowski assembly.
Figure 25. Neutral Bus Rogowski ASM 10108266