EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Table 8. WavePro secondary disconnect terminals and standard connections.
A Disconnect Block (left side from front)
C Disconnect Block (right side from front)
10
Aux Switch (NO contact)
10
Aux Switch (N.O. contact)
1
Aux Switch
1
Aux Switch
2
Aux Switch
2
Aux Switch
11
Aux Switch (NC contact)
11
Aux Switch (NC contact)
12
Aux Switch (NO contact)
12
Aux Switch (NO contact)
3
Aux Switch
3
Aux Switch
4
Aux Switch
4
Aux Switch
13
Aux Switch (NC contact)
13
Aux Switch (NC contact)
5
Aux Switch (NO contact)
14
Second Shunt Trip
6
Aux Switch (NC contact)
5
Second Shunt Trip2
7
Aux Switch (common)2
OR
OR
14
Aux Switch (NO contact)
5
Shunt Trip (NO contact)
5
Aux Switch2
6
Shunt Trip (NC contact)
7
Shunt Trip (common)2
6
Aux Switch
14
Bell Alarm (NO contact)
15
Aux Switch (N.C. contact)
15
Bell Alarm (NC contact)
8
Remote Charge Indicator
16
Bell Alarm (common)
17
Remote Charge Indicator
19
Bell Alarm (NO contact)
16
WP-50 Fan Motor- 120Vac (H)
20
Bell Alarm (NC contact)
7
WP-50 Fan Motor- 120Vac (N)
21
Bell Alarm (common)
9
CMD PH
8
Closing Spring Charging Motor
18
NI Set
17
Closing Spring Charging Motor
19
NI Set
9
Close Circuit1
20
NI Reset
18
Close Circuit1
21
NI Reset
22
Undervoltage or Electric Lockout
22
OFLO (phase A)
23
Undervoltage or Electric Lockout
23
OFLO (phase A)
24
Neutral Sensor – tap (+)
24
OFLO (phase B)
25
Neutral Sensor – common (-)
25
OFLO (phase B)
26
Modbus RX (-)
26
OFLO (phase C)
27
Modbus TX (+)
27
OFLO (phase C)
28
Zone Selective Interlock (In+)
28
Output 2
29
Zone Selective Interlock (In–)
29
NI NO
30
Zone Selective Interlock (Out+)
30
NI COMM
31
Zone Selective Interlock (Out–)
31
Input 2
32
Va (voltage conditioner)
32
Output 2
33
Vb (voltage conditioner)
33
Output1/ RELT/GFA
3
34
Vc (voltage conditioner)
34
Output1/ RELT/GFA
3
35
Trip Unit Aux Pwr (24 Vdc+)
35
Input 1/RELT
3
36
Trip Unit Aux Pwr (24 Vdc–)
36
Input COMM
3
1
For electrically operated breaker; Remote Close accessory on manually operated breaker.
2
Auxiliary Switch contacts are wired out if Shunt Trip is not provided.
3
33, 34, 35 & 36 – If RELT is optioned, then 33, 34, 35 & 36 are permanently assigned as RELT Output and Input.
Note : A small number of specially wired WavePro breakers had a Normally Closed Remote Charge Indicator switch contact wired out to
WavePro 36 Pt secondary disconnect points C9 & C18 for use in a motor protection circuit in AKD-10 switchgear. This functionality is not
required by the Retrofill breaker. The NMICV timer and MC control relay’s 4 parallel contacts in the switchgear should be eliminated from the
circuit. 120VAC continuous power should be applied to WavePro/ AKD-10 36-point secondary disconnect terminals A8 & A17