44
EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
4.
Inside the compartment, check the contact areas on each primary disconnect bar or cluster of fingers for
foreign matter that may have accumulated. Clean those areas if necessary with a clean, lint-free rag and
isopropyl alcohol or acetone.
5.
Be sure to apply a thin film of red Mobilgrease 28 to the primary disconnect contact areas for better
electrical connections inside the compartment. This is available in 1 oz. tubes, GE part # 193A1751P1.
Install Secondary Disconnect Spacer Block (800-2000A ONLY)
Install the spacer block provided as shown in
Figure 31
, below. Remove the protective tape on the block and
stick it on the secondary disconnect mounting plate as shown in
Figure 31
. Be sure the spring is moved to the
front of the spacer block.
Optional
: The hole in the spacer block can be used to add a 10-32 screw. Drill a 0.177”(4.5mm) hole in the
steel plate above and install 10-32 taptite thread forming screw ( GE part: N722P16012B6)
Note
: Use a #16 Std or 4.5mm metric drill bit Use 5/16” hex to install screw to 45-50 in-lbs Torque.
Figure 31. AKD-10 Secondary Disconnect Spacer Block ( 800-2000A ONLY )
Install New Door
1.
To remove existing compartment door(s), refer to your manual on how to remove the legacy doors.
2.
To install the new door, refer to the
Retrofill Doors Assemblies for AKD-5, AKD-6, AKD-8 & AKD-10, DEH-
41563
.
Rear support
Spacer
block