26
EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
AKD-10—Install Accessories
WIRING
•
Before installing the breaker, the
secondary disconnects must be wired
to the EntelliGuard R Breaker.
•
Wires with wire markers are provided
on the breaker . Make sure that the
switchgear wiring connection points
match up with the original wiring of the
cubicle. This ensures that all wiring
connections are properly made.
•
Wrong connections will cause the
breaker to malfunction.
AKD-10—Secondary Disconnects
This section deals with installing and wiring the legacy secondary disconnect assemblies onto the
EntelliGuard R breaker . Installing the secondary disconnect assembly consists of doing these tasks:
•
Installing the secondary disconnect assembly (
Figure 14, Figure 15, and Figure 16
).
•
Wiring the secondary disconnect assembly (
Table 8
shows the WavePro secondary disconnect terminals)
.
The EntelliGuard R Retrofill Breaker has these three options:
•
One secondary disconnect installed
•
Two secondary disconnects installed
•
No secondary disconnects installed
Figure 14. AKD-10 Secondary Disconnects View 1
Figure 15. AKD-10 Secondary Disconnects View 2