BI connectors diagram and terminal polarity of the B2 board (6 BI + 8 BO)
Connectors diagram and terminal polarity of the B1 board (16 BI) for
terminals 17 to 26.
For information about the digital inputs specifications, refer to Technical Specifications
Chapter.
The DR60 can work with up to 100% of its digital inputs and 50% of its digital outputs
energized simultaneously at the maximum ambient temperature (considering the
maximum number of inputs/output available).
Connections shall use screened/shielded cables with insulated flexible wires of 1.5 mm²
cross section, voltage rating of 300Vrms.
4.8.2
Binary Outputs
The digital outputs can be used to control switching units (circuit breaker and recloser,
for example) and announcements for remote signaling of events and status.
Each module has eight digital output channels. The digital outputs are shown in figure
below.