![GE DR60 Technical Manual Download Page 59](http://html.mh-extra.com/html/ge/dr60/dr60_technical-manual_133551059.webp)
DR60
59
DR60-TM-EN-
2A
Card not detected, invalid
or incompatible
BSE/ALARMSGGIO1.ST.Alm2
Happens when there are
discrepancies between the
installed boards and the
device CORTEC
Internal voltage
BSE/ALARMSGGIO1.ST.Alm3
Internal voltage
automonitoring alarm
Internal temperature
BSE/ALARMSGGIO1.ST.Alm4
Internal temperature is
abnormal (Out of -10°C to
60ºC)
No communication
Ethernet interface 1
BSE/ALARMSGGIO1.ST.Alm5
Loss of communication
with ethernet interface 1
Waveform/Fault recorder
memory usage above 98%
BSE/ALARMSGGIO1.ST.Alm6
Happens when the
memory becomes 98% full
for waveform recorder
Disturbance recorder
memory usage above 98%
BSE/ALARMSGGIO1.ST.Alm7
Happens when the
memory becomes 98% full
for disturbance recorder
Trend recorder memory
usage above 98%
BSE/ALARMSGGIO1.ST.Alm8
Records memory exceeds
98% for trend recorder
SOE recorder memory
usage above 98%
BSE/ALARMSGGIO1.ST.Alm9
Records memory exceeds
98% for SOE recorder
GOOSE subscriber failure
or timeout
BSE/ALARMSGGIO1.ST.Alm10
Time for the next expected
GOOSE message to come
exceeded
Warnings
Data Name
Description
Sync OK
BSE/ALARMSGGIO1.ST.Wrn1
Equipment not sync
No communication
Ethernet interface 2
BSE/ALARMSGGIO1.ST.Wrn5
Loss of communication
with ethernet interface 2
Waveform/Fault recorder
memory usage above 90%
BSE/ALARMSGGIO1.ST.Wrn6
Happens when the
memory becomes 90% full
for waveform recorder
Summary of Contents for DR60
Page 12: ...12 DR60 TM EN 2A ptpd internal BSD ...
Page 24: ......
Page 78: ......
Page 93: ...DR60 93 DR60 TM EN 2A Binary inputs and outputs of the B2 board 8 BO 6 BI ...