DR60
66
DR60-TM-EN-
2A
Basic
Voltage total harmonic distortion
MET/MHAI.ThdPhV.phsC.cVal.mag.f
MMXN
Fundamental
Frequency
MET/MMXN.Hz.mag.f
Fundamental
Voltage (RMS)
MET/MMXN.Vol.mag.f
Fundamental
Current (RMS)
MET/MMXN.Amp.mag.f
Fundamental
Phase active power
MET/MMXN.Watt.mag.f
Fundamental
Phase reactive power
MET/MMXN.VolAmpr.mag.f
Fundamental
Phase apparent power
MET/MMXN.VolAmp.mag.f
Others
Phase power factor
MET/MMXN.PwrFact.mag.f
MHAN
Basic
Current total harmonic distortion
MET/MHAN.ThdAmp.mag.f
Basic
Voltage total harmonic distortion
MET/MHAN.ThdVol.mag.f
TGSN
Transducer (magnitude)
MET/TGSN.GenSv.instMag.f
Digital inputs
GOOSE inputs
DIG/GOOSEGGIO1
Digital inputs
DIG/DIGITALGGIO1
Digital outputs
DIG/OUTPUTGGIO1
3.2
Recording Times by Trigger
Once triggered, the following parameters are considered by the disturbance recorder:
Parameter
Allowed values
Increment
Pre-fault time (
t
pre
)
0 … 2
min
0.1 min
Post-fault time (
t
pos
)
0 … 60
min
0.1 min
Maximum Record time (
t
max
)
1 … 60
min
0.1 min
The Maximum Record time configures the maximum duration that the register can
reach. If consecutive retriggers or a sustained fault happens, the Maximum Record time
establishes the limit of time that the COMTRADE file will register.
The maximum duration of the disturbance record is 60 minutes.