DR60
44
DR60-TM-EN-
2A
▪
Network Settings
▪
APP ID: inserts an indication of the message identifier. The identifier must
contain four hexadecimal characters. Characters range 0x0
–
0x3FFF.
▪
MAC-Address: inserts an indication of the MAC address of the originator to be
filtered. The address must be represented as six groups of hexadecimal
characters. The allowed characters are 0-9, a-f, A-
F and ‘
-
‘.’. IEC 61850
-8-1
standard recommends the MAC address for GOOSE messages creation as
following:
▪
The first three bytes are 01-0C-CD;
▪
The fourth byte must be 01 for GOOSE;
▪
Thus, the MAC address must be from 01-0C-CD-01-00-00 to 01-0C-CD-01-
01-FF.
▪
VLAN-PRIORITY: selects the VLAN priority. Such priority must be a numeric value
between 0 and 7.
▪
VLAN-ID: inserts the VLAN unique identification. Characters range 0x0
–
0xFFF.
▪
Minimum Time: inserts the maximum delay time allowed for message
transmission, after the change of the state. The range is from 1 ms to 60000 ms.
▪
Maximum Time: inserts the source supervision time. If there is none change of
state, a message is transmitted in this time. The range is from 4 ms to 60000 ms.
5.4.4
GOOSE Subscriber
The DR60 has 256 virtual GOOSE inputs that can be associated with GOOSE Booleans
values.
The configurable parameters are described below:
To associate a GOOSE Control Block with a digital input, do the following:
1
Load the SCL file from the IED sending the messages clicking “Add SCL File”
.
2
On the right side, select the GOOSE Boolean that the DR60 shall subscribe to, on the
right side select the GOOSE input that will be associated with that GOOSE boolean. Only
the GOOSE inputs enabled in the Binary configuration tab will be displayed.
3
Click the
“>>”
button
to perform the association and “<<” to undo it.
5.4.5
Reports
This screen allows the user to configure the MMS Report Control Blocks (RCB). The
Report Control Block sends internal variables grouped on a datasheet to the supervisory
system.
Each RCB is associated to one Dataset and the DR60 is able to send up to 15 buffered or
unbuffered Report Control Blocks.
The configurable parameters are described below:
Summary of Contents for DR60
Page 12: ...12 DR60 TM EN 2A ptpd internal BSD ...
Page 24: ......
Page 78: ......
Page 93: ...DR60 93 DR60 TM EN 2A Binary inputs and outputs of the B2 board 8 BO 6 BI ...
Page 106: ......