MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 37 of 118
Overtravel
The overtravel is also monitored for each operation. This is defined as the difference (in
mm) between these two measured values:
-
The maximum travel point reached during the operation
-
The final resting position at the end of the operation
as measured by the travel sensor and shown on the travel curve
Figure 52
–
Monitoring the overtravel
HMI: Measurements/Last opening results and Last closing results
Figure 53
–
Overtravel display
An alarm threshold can be entered for the maximum overtravel:
HMI: Settings/Operations monitoring
Figure 54
–
Setting the overtravel threshold