MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 32 of 118
Timing alarms
Alarm thresholds can be set for the following measured items:
Opening - (all CB)
•
Minimum and maximum Reaction time (t1), per pole
•
Minimum and maximum Operation time (t2), per pole
•
Minimum and maximum Travel time (t2-t1), per pole
•
Minimum contact separation speed, per pole
Opening - (IPO CB only)
•
Maximum t1 pole to pole discordance
•
Maximum t2 pole to pole discordance
•
Maximum t2-t1 pole to pole discordance
Closing - (all CB)
•
Minimum and maximum Reaction time (t1), per pole
•
Minimum and maximum Operation time (t2), per pole
•
Minimum and maximum Travel time (t2-t1), per pole
Closing
–
(IPO CB only)
•
Maximum t1 pole to pole discordance
•
Maximum t2 pole to pole discordance
•
Maximum t2-t1 pole to pole discordance
The threshold values can be entered during setup here:
HMI: Settings/Opening and Settings/Closing
Figure 44
–
Operation timing alarms thresholds
An alarm is raised if, for any of the poles, the measured/calculated value during an opening
or closing operation is found to be beyond the thresholds set (i.e. below the minimum value
or above the maximum value set).